Overview of functions
5.3 Safety-oriented tripping
SIMOCODE pro
52
System Manual, 05/2019, A5E40507475002A/RS-AD/004
5.3
Safety-oriented tripping
The SIMOCODE pro motor management system has two modules for the safety-related
tripping of motors:
●
Fail-safe digital module DM-F local: For applications requiring safety-related tripping of a
motor feeder via a hardware signal that is acquired and evaluated by the module.
●
DM-F PROFIsafe fail-safe digital module: For applications that require the safety-related
tripping of a motor feeder by a fail-safe controller (F-CPU) via the communication bus with
the fail-safe PROFIsafe profile.
These modules conform to the general requirements for EMERGENCY STOP devices or
safety circuits described in EN 418 and EN 60204-1 (06.2006).
Depending on the external circuit, the following Performance Level / Safety Integrity Level
can be achieved:
●
PL e with Category 4 according to ISO 13849-1 or
●
SIL 3 according to IEC 61508/62061
Safety technology and safety-related functions
●
Are exclusively restricted to the fail-safe digital modules.
●
Do not directly affect existing SIMOCODE pro components and concepts.
A more detailed description is provided in the documentation listed below
●
Manual Fail-safe Digital Modules SIMOCODE pro, German
https://support.automation.siemens.com/WW/view/de/50564852
●
Manual Fail-safe Digital Modules SIMOCODE pro, English
https://support.automation.siemens.com/WW/view/de/50564852/0/en
●
Manual Fail-safe Digital Modules SIMOCODE pro, French
https://support.automation.siemens.com/WW/view/de/50564852/0/fr
●
Manual Fail-safe Digital Modules SIMOCODE pro, Spanish
https://support.automation.siemens.com/WW/view/de/50564852/0/es
●
Operating instructions "Fail-Safe Digital Module DM-F Local"
https://support.automation.siemens.com/WW/view/en/49222263
●
Operating instructions "Fail-Safe Digital Module DM-F PROFIsafe"
https://support.automation.siemens.com/WW/view/en/49222281
You will find the System Manuals and Operating Instructions at Manuals/operating
instructions (
https://support.industry.siemens.com/cs/ww/en/ps/16027/man
CAUTION
Loss of safety function is possible
For the 24 V DC power supply, always use an SELV or PELV power supply unit!
For capacitive and inductive loads, an adequate protective circuit is required!
Summary of Contents for SIMOCODE pro C
Page 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Page 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...