SIMO_CHN Function
3.6 Display in WinCC
SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2
50
Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001
Faults view
①
Record 130, Byte 6 (CS_6)
②
Record 130, Byte 7 (CS_7)
③
Record 130, Byte 8 (CS_8)
④
Update (CS_UPD, QENSDCS)
When a picture is selected, CS_UPD is set. Status bytes CS_6, CS_7, and CS_8 are linked
to I/O fields (hidden). In these I/O fields, the "Flashing Background Active" property is
enabled in displays CS_60..67, CS_70..77 or CS_80..87 by means of C-scripts. This
indicates which bits are set in the status byte. The colors of the individual indicators can be
defined through the "Background Flashing Color On" and "Background Flashing Color Off"
property.
Input Update requires operator level5; operator enabling at login is linked through the direct
connection of picture element @Level5 (Operator Enabling) -> Permissions (Operator
Enabling). The operator enabling and background colors for the other I/O fields are then
defined in the "Permissions" picture element by means of a C-script.