Product Overview
1-5
High Speed Counter Encoder Module User Manual
The HSCE module allows you to connect counters internally for cascaded
counting. The module also provides Immediate I/O operation as well as
Interrupt I/O capability (using Task 8 to execute interrupt handling
routines). To continue the counting operation in case of a loss of power to the
I/O base, you can provide back-up power to the module.
NOTE:
The listed CPU Software releases may not properly allow the module
to update the WX words during an immediate I/O Read cycle. If you use one
of the releases listed below, use an immediate I/O Write following the
immediate I/O Read to correct a possible conflict:
•
SIMATIC TI545, Release 2.1.1 and earlier.
•
SIMATIC TI555, Release 1.1.2 and earlier.
Additional Module