Specifications
C-8
High Speed Counter Encoder Module User Manual
Output Specifications (continued)
The module software cycle time is less than 1 millisecond. The typical
response times of input to output signals are listed in Table C-4.
Table C-4
Module Response Times
Counter 1 to output 1
Less than 10 microseconds
Counter 1, Preset 2 to output 1
Less than 1 millisecond
Counter 1, Preset 2 to output 2
Less than 1 millisecond
Counter 2 to output 3
Less than 10 microseconds
Counter 3 to output 4
Less than 10 microseconds
Counter 4 to output 5
Less than 10 microseconds
Counter 4, Preset 6 to output 5
Less than 1 millisecond
Counter 4, Preset 6 to output 6
Less than 1 millisecond
Counter 5 to output 7
Less than 10 microseconds
Counter 6 to output 8
Less than 10 microseconds
The Backup Power Supply must be rated at 12 V
"
20 per cent at 200
milliamperes maximum. The supply must be a Class 2 power supply.
Module Response
Times
Backup Power
Supply
Specifications