Installing the Module
2-5
386/ATM Coprocessor User Manual
2.3
Inserting the Module into the Base
To minimize potential shock, turn off power to the I/O base and to
any modules installed in the base before you insert or remove a
module or install a terminal block. Failure to do so may result in
potential injury to personnel or damage to equipment.
Refer to the Safety Considerations sheet (part # 2588015–0002)
included with your module for a complete list of safety guidelines
and recommendations.
This is a triple-wide module. Insert it into any available I/O slot on any
Series 505 base. Insert the module as shown in Figure 2-4. Note the
minimum torque required to ground the module.
Minimum torque: 2.6 in-lb (0.3N-m)
Maximum torque: 4.12 in-lb (0.6N-m)
Backplane connectors
A000329
Figure 2-4
Inserting the Module into the Base
This module requires 11.0 W of +5 V and 0.2 W of –5 V power from the
Series 505 base. No additional power is required.
WARNING
!
Inserting the
Module
Power
Requirements