1-3
SIMATIC TD 200 Operator Interface
C79000-G7076-C272-01
Table 1-1
Components of the TD 200, Fortsetzung
Component
Description
Keys
The TD 200 has nine keys. Five of these keys provide predefined,
context-sensitive functions, and four keys provide user-defined functions.
Spacers
Self-adhesive spacers are included for mounting the TD 200 to a mounting
surface. See Figure 1-7.
TD 200 Keyboard Features
The TD 200 keyboard has a total of nine keys. Table 1-2 describes the five
predefined, context-sensitive command keys.
Table 1-2
Description of Command Keys
Command
Keys
Description
ENTER
Use this key to write new data and to acknowledge a message(s).
ESC
Use this key to toggle between Display Message mode and Menu mode
or to abort an edit.
UP ARROW
The UP arrow increments data and scrolls the cursor to the next higher
priority message.
DOWN ARROW
The DOWN arrow decrements data and scrolls the cursor to the next
lower priority message.
SHIFT
The SHIFT key modulates the value of all of the function keys. See
Table 1-3 for examples. A flashing “S” is displayed in the lower right of
the TD 200 display when you press the SHIFT key.
Table 1-3 describes the four user-defined function keys (F1, F2, F3, F4). You
define these four function keys in your S7-200 CPU program. Pressing a function
key sets an M bit. Your program can use this bit to trigger a specific action.
Table 1-3
Description of Function Keys
Function Keys
Description
F1
Function key F1 sets the Mx.0 bit.
If you press the SHIFT key along with, or prior to, pressing the F1 key,
F1 sets the Mx.4 bit.
F2
Function key F2 sets the Mx.1 bit.
If you press the SHIFT key along with, or prior to, pressing the F2 key,
F2 sets the Mx.5 bit.
F3
Function key F3 sets the Mx.2 bit.
If you press the SHIFT key along with, or prior to, pressing the F3 key,
F3 sets the Mx.6 bit.
F4
Function key F4 sets the Mx.3 bit.
If you press the SHIFT key along with, or prior to, pressing the F4 key,
F4 sets the Mx.7 bit.
Product Overview and Installation
Summary of Contents for SIMATIC TD 200
Page 22: ...1 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Product Overview and Installation ...
Page 84: ...A 12 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Specifications and Reference ...
Page 94: ...B 10 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Multiple CPU Configurations ...
Page 126: ...E 6 SIMATIC TD 200 Operator Interface C79000 G7076 C272 01 Modifying a TD 200 Configuration ...