EIP-200S Ethernet/IP Adapter
2.5 Replacing a faulty EIP-200S Adapter
EIP-200S Ethernet/IP Adapter Distributed I/O System
24
System Manual, 06/2018, A5E44345053-AB
Network Status LED is solid red
The device fails the duplicate MAC ID check sequence during power-up due to a conflicting
node ID.
To recover, perform one of the following steps:
●
If the EIP-200S Ethernet/IP Adapter is using DHCP, change the IP address at the DHCP
server and power cycle the EIP-200S.
●
If using a configured IP address, modify one of the IP addresses with the ZNX-EIP-200S
Configuration Tool. You may have to disconnect one of the conflicting devices from the
network first.
Network Status LED flashing red
If the Network Status LED is flashing red, one or more I/O connections are in the time-out
state. This can be caused by the controller stopping I/O without closing the connection or by
a break in Ethernet communications.
I/O Status LED flashing red
If the I/O Status LED is flashing red, one or more of the inputs/outputs are faulted when I/O
is active. This only occurs if an I/O connection is open (Network Status LED is solid green).
This may be caused by a diagnostic alarm due to a short circuit on an output module, a
missing module due to hot swapping, or a missing terminating module.
2.5
Replacing a faulty EIP-200S Adapter
When a new configuration or new network parameters are downloaded to the EIP-200S
Ethernet/IP Adapter, the data is stored in the SD memory card if it is installed. When an
Adapter is replaced, the SD card can be used to transfer the configuration and network
parameters to the replacement Adapter.
In case of Adapter failure, follow this process to replace the Adapter:
1.
Prepare and mount the replacement Adapter.
2.
Transfer the SD card from the old Adapter to the replacement Adapter.
3.
Power up the Adapter so it will read the SD card and set the configuration in nonvolatile
memory.
4.