Using I/Os in S7–400H
13.3 Using single-channel switched I/O
S7-400H
System Manual, 03/2012, A5E00267695-11
173
13.3
Using single-channel switched I/O
What is single-channel switched I/O?
In the single-channel switched configuration, the input/output modules are present singly
(single-channel).
In redundant mode, these can addressed by both subsystems.
In standalone mode, the master subsystem can always address all switched I/Os (in contrast
to one-sided I/O).
Single-channel switched I/O configuration at the PROFIBUS DP interface
The system supports single-channel switched I/O configurations containing an ET 200M
distributed I/O module with active backplane bus and a redundant PROFIBUS DP slave
interface module.
6+DXWRPDWLRQV\VWHP
(7b0'LVWULEXWHG,2
5DFN
5DFN
Figure 13-1 Single-channel switched distributed I/O configuration at the PROFIBUS DP interface
You can use the following interfaces for the I/O configuration at the PROFIBUS DP interface:
Table 13- 1 Interfaces for use of single-channel switched I/O configuration at the PROFIBUS DP
interface
Interface
Order number
IM 153–2
6ES7 153–2BA81–0XB0
6ES7 153–2BA02–0XB0
6ES7 153–2BA01–0XB0
6ES7 153–2BA00–0XB0
IM 153–2FO
6ES7 153–2AB02–0XB0
6ES7 153–2AB01–0XB0
6ES7 153–2AB00–0XB0
6ES7 153–2AA02–0XB0
Each S7–400H subsystem is interconnected with one of the two DP slave interfaces of the
ET 200M via a DP master interface.