8.3.2
Bus connector
Wiring
Only with 6ES7467-5GJ02-0AB0.
The bus cable is connected to the IM 467 by means of this connector. (See the detailed
description in the section on networking in the
S7-400, Hardware and Installation manual.)
1
2
3
Figure 8-3
Connecting the bus connector to the IM 467
(1)
Switch for bus terminator resistor
(2)
PROFIBUS_DP bus line
(3)
Bus connector
Maximum cable lengths for PROFIBUS DP
Transmission speed
in Kbps
9,6
19,2
93,75
187,5
500
1500
3000
6000
12000
Max. length of a bus
segment in m
1.000
1.000
1.000
1.000
400
200
100
100
100
Max. number of bus
segments 1
10
10
10
10
10
10
10
10
10
Max. length in m
10.000 10.000 10.000 10.000 4.000
2.000
1.000
1.000
1.000
1
Bus segments are interconnected with RS 485 repeaters
PROFIBUS DP master interface IM 467/IM 467 FO
8.3 Connection to PROFIBUS DP
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
369