Representation of analog values for Ni x00 standard resistance thermometers
Table 5-18
Analog value representation for resistance thermometers Ni100, 120, 200, 500, 1000
Ni x00
Standard in
°C (1 digit =
0.1° C)
Unit dec‐
imal
Unit hex‐
adeci‐
mal
Ni x00
Standard in
°F (1 digit =
0.1 °F)
Unit dec‐
imal
Unit hex‐
adeci‐
mal
Ni x00
standard in
K (1 digit =
0.1 K)
Unit dec‐
imal
Unit hex‐
adeci‐
mal
Range
> 295,0
32767
7FFF
H
> 563,0
32767
7FFF
H
> 568,2
32767
7FFF
H
Overflow
295,0
2950
B86
H
563,0
5630
15FE
H
568,2
5682
1632
H
Overshoot
range
:
:
:
:
:
:
:
:
:
250,1
2501
9C5
H
482,1
4821
12D5
H
523,3
5233
1471
H
250,0
2500
9C4
H
482,0
4820
12D4
H
523,2
5232
1470
H
Nominal range
:
:
:
:
:
:
:
:
:
-60,0
-600
FDA8
H
-76,0
-760
FD08
H
213,2
2132
854
H
-60,1
-601
FDA7
H
-76,1
-761
FD07
H
213,1
2131
853
H
Undershoot
range
:
:
:
:
:
:
:
:
:
-105,0
-1050
FBE6
H
-157,0
-1570
F9DE
H
168,2
1682
692
H
< -105,0
-32768
8000
H
< -157,0
-32768
8000
H
< 168,2
32768
8000
H
Underflow
Representation of analog values for Ni x00 climatic resistance thermometers
Table 5-19
Analog value representation for resistance thermometers Ni 100, 120, 200, 500, 1000
Ni x00 Cli‐
matic in °C
(1 digit =
0.01° C)
Unit dec‐
imal
Unit hex‐
adeci‐
mal
Ni x00 Cli‐
matic in °F
(1 digit =
0.01 °F)
Unit dec‐
imal
Unit hex‐
adeci‐
mal
Range
> 295,00
32767
7FFF
H
> 325,11
32767
7FFF
H
Overflow
295,00
:
250,01
29500
:
25001
733C
H
:
61A9
H
327,66
:
280,01
32766
:
28001
7FFE
H
:
6D61
H
Overshoot range
250,00
:
-60,00
25000
:
-6000
61A8
H
:
E890
H
280,00
:
-76,00
28000
:
-7600
6D60
H
:
E250
H
Nominal range
-60,01
:
-105,00
-6001
:
-10500
E88F
H
:
D6FC
H
-76,01
:
-157,00
-7601
:
-15700
E24F
H
:
C2AC
H
Undershoot range
< -105,00
-32768
8000
H
< -157,00
-32768
8000
H
Underflow
Analog modules
5.4 Representation of analog values
S7-400 Automation System Module Data
178
Reference Manual, Ausgabe 11/2016, A5E00850736-08