5.4.4
Configuration Data of the 3964(R) Procedure
Introduction
Using the parameter assignment data of the 3964(R) procedure, you can adjust the CP 440
to suit the properties of its communication partner.
Configuration Data of the 3964(R) Procedure
With the CP 440: Point-to-Point Communication, Parameter Assignment interface, specify
the parameters for the physical layer (layer 1) and the data-link layer (layer 2) of the 3964(R)
procedure. Below you will find a detailed description of the parameters.
Note
The 3964(R) procedure can only be used in four-wire mode.
Protocol
The following table describes the protocol.
Table 5-10 3964(R) Protocol
Parameters
Description
Default Value
3964 with default
values and no
block check
•
The protocol parameters are set to default values.
•
If the CP 440 recognizes the string DLE ETX, it stops receiving
and sends a DLE to the communication partner if the block was
received undamaged, or an NAK if it was damaged.
3964(R) No
Default Values
With Block Check
•
The protocol parameters are set to default values.
•
If the CP 440 recognizes the string DLE ETX BCC, it stops
receiving and compares the received block check character with
the longitudinal parity calculated internally. If the BCC is correct
and no other receive errors have occurred, the CP 440 sends
the code DLE to the communication partner. If the BCC is
correct and no other receive errors have occurred, the CP 440
sends the code DLE to the communication partner (the NAK
code is sent if an error occurs).
3964
programmable
without block
check
•
The protocol parameters are programmable.
•
If the CP 440 recognizes the string DLE ETX, it stops receiving
and sends a DLE to the communication partner if the block was
received undamaged, or an NAK if it was damaged.
3964(R) No
Default Values
With Block Check
•
The protocol parameters are programmable.
•
If the CP 440 recognizes the string DLE ETX BCC, it stops
receiving and compares the received block check character with
the longitudinal parity calculated internally. If the BCC is correct
and no other receive errors have occurred, the CP 440 sends
the code DLE to the communication partner. If the BCC is
correct and no other receive errors have occurred, the CP 440
sends the code DLE to the communication partner (the NAK
code is sent if an error occurs).
3964(R) Default Values With
Block Check:
CDT = 220 ms
ADT = 2000 ms
Setup attempts = 6
Transmission attempts = 6