IP 240
Position Decoding
FB 26 LEN=75
0030 :JC =CHEK
0031 :JU =END
0032 PRO2 :
0033 :L FW 14 -ANALOG VAL IF DOWN COUNTING,
0034 :L KB 0 RESET OUTPUTS
0035 :<F
0036 :JC =CHEK
0037 :JU =END
0038 CHEK:
0039 :R Q 12.1 -RUNNING
003A :R Q 12.2 -ENABLED
003B :S Q 12.3 -RET INTPNT
003C :R Q 12.4 -HEATING
003D :L KB 0
003E :T FY 12 AUXILIARY FLAGS
003F :T FW 14 -ANALOG VAL
0040 END :
0041 :***
I 4.0 = EMERG STOP
Q 12.0 = STOPPED EMERG STOP PRESSED
FY 10 = CHECK BYTE IMAGE OF FB11 IN CASE OF ERROR
Q 12.5 = FAULT FAULT FLAG FROM CONTROLLER (IP)
I 4.6 = LMTSW FORW LIMIT SWITCH FURNACE FORWARD
I 4.7 = LMTSW BACK LIMIT SWITCH FURNACE BACKWARD
FY 2 = AUX BYTE1 SCRATCH FLAG BYTE CYCLIC PROGRAM
Q 12.4 = HEATING HEATING ON (CON INDICATOR)
FW 14 = ANALOG VAL ANALOG VALUE TO BE OUTPUT IN UNITS (MAX 1024)
Q 12.1 = RUNNING RUN STARTED
Q 12.2 = ENABLED NEW RUN POSSIBLE
Q 12.3 = RET INTPNT INITIAL POINT MUST BE TRANSFERRED BEFORE RESTARTING
NETWORK 2 0042 OUTPUT OF SPEED
0042 :L FW 14 -ANALOG VAL ADAPTATION TO FORMAT OF
0043 :SLW 4 THE ANALOG OUTPUT
0044 :T PW 128 ADDRESS OF ANALOG OUTPUT
0045 :BE
FW 14 = ANALOG VAL ANALOG VALUE TO BE OUTPUT IN UNITS (MAX 1024)
EWA 4NEB 811 6120-02a
7-53