Certification
6.3 EMC and Environmental Type Tests
6.3
EMC and Environmental Type Tests
The RUGGEDCOM MX5000 has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure Contact
+/- 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
+/- 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Note
Signal ports
+/- 4 kV @ 2.5 kHz
Note
DC Power ports
+/- 4 kV
4
AC Power ports
+/- 4 kV
4
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports
+/- 4 kV
4
Signal ports
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
4
DC Power ports
+/- 2 kV line-to-earth,
+/- 1 kV line-to-line
3
IEC 61000-4-5
Surge
AC Power ports
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
4
Signal ports
10 V
3
D.C Power ports
10V
3
AC Power ports
10V
3
IEC 61000-4-6
Induced
(Conducted) RFI
Earth ground ports
10V
3
100 A/m
IEC 61000-4-8
Magnetic Field
Enclosure Ports
1000 A/m for 1 s
5
DC Power ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
IEC 61000-4-29
Voltage Dips
& Interrupts
AC Power ports
30% for 1 period,
60% for 50 periods
IEC 61000-4-11
Voltage Dips
& Interrupts
AC Power ports
100% for 5 periods,
100% for 50 periods
Signal ports
2.5 kV common, 1 kV
differential mode @1 MHz
3
DC Power ports
2.5 kV common, 1 kV
differential mode @1MHz
3
IEC 61000-4-12 Damped Oscillatory
AC Power ports
2.5 kV common, 1 kV
differential mode @1MHz
3
Signal ports
30 V Continuous,
300 V for 1 s
4
IEC 61000-4-16
Mains Frequency
Voltage
DC Power ports
30 V Continuous,
300 V for 1 s
4
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power ports
10%
3
IEC 60255-5
Dielectric Strength
Signal ports
2 kV (Fail-Safe
Relay output)
42
RUGGEDCOM MX5000
Installation Manual, 01/2021, C79000-G8976-1059-13