Technical specifications
7.4 Technical data
SIMATIC IPC327G
Operating Instructions, 09/2021, A5E51366275-AA
59
7.4
Technical data
7.4.1
General technical specifications
General technical specifications
Weight
Approx. 1.8 kg
Power supply
1
•
24 V DC (19.2 to 28.8V)
Power consumption (DC)
•
40%~60% full load, 24 V DC at 85% efficiency
•
Pout
≥
6W, 24 V DC at 70% efficiency
•
Pout < 6W, 24 V DC at 50% efficiency
Current consumption
•
Max. 2.5 A at 24 V
Noise emission
< 55 dB(A) according to DIN 45635-1
Degree of protection
IP40 in accordance with IEC 60529
Protection class
Class III
Overvoltage Category
II
Pollution Degree
2
Quality assurance
In accordance with ISO 9001
1
The device may only be connected to a 24 V DC power supply which meets the require-
ments of a safe extra-low voltage (SELV) or protective extra-low voltage (PELV) in accord-
ance with IEC/EN/DIN EN/UL 61010-2-201.
Electromagnetic compatibility
Radiation Emission (Enclosure port)
in accordance with IEC 61000-6-4
+ A1/ CAN/CSA-CISPR 22:10
•
30 to 230 MHz: 40 dB(µV/m) Quasi-peak (10 m distance)
•
230 to 1000 MHz: 47 dB (µV/m) Quasi-peak (10 m distance)
•
1 to 3 GHz: 70 dB (µV/m) Peak; 56 dB (µV/m) Average (3 m
distance)
•
3 to 6 GHz: 80 dB (µV/m) Peak; 60 dB (µV/m) Average (3 m
distance)
Immunity with regard to conduct-
ed interference on the supply lines
•
± 2 kV (5 kHz /100 kHz) in accordance with IEC 61000-4-4;
Burst
•
± 1kV line to line, ±2 kV line to earth in accordance with IEC
61000-4-5; Surge