Technical Data
A-5
SICALIS PMC 7 Operator Panel Equipment Manual
Release 09/00
Conformity of the product described with the requirements of Directive 89/336 EEC
is certified by compliance with the following standards:
Immunity to Interference
Static discharge
(contact discharge/air discharge)
EN 61000-4-2
6 kV/8 kV
HF radiation
EN 61000-4-3
10 V/m, 80% AM,
1 kHz
Pulse modulation
ENV 50204
900 MHz
±
5 MHz
10 V/m
eff.
, 50% ED, 200 Hz
HF current
EN 61000-4-6
150 kHz – 80 MHz
10 V, 80% AM, 1 kHz
Burst interference
Mains supply lines
Supply lines
Process data lines
Signal lines
EN 61000-4-4
2 kV
2 kV
2 kV
1 kV
Interference Emission
Radio interference suppression in accord
with EN 55011
Class A