Test: Switch on the supply on the power supply module. If the connections are correct, LEDs “DC 5V”

(green) on the CPU and FM 357-2 will light up.

Installing firmware from the memory card

Proceed as follows:

Insert the memory card with the firmware to be installed into the control switched-off.

Switch the start-up switch to position A.

Switch the control “ON” 

 the system software and data are transferred from the memory card to the

control.

The “SF” LED lights up and the “DIAG” LED flashes cyclically four times during the data transfer.

An error is indicated in the following cases (see Manual Table 11-2):

If the “SF” LED flashes (2 Hz). The firmware cannot be transferred to the internal memory of the
FM (e.g. system software on the internal memory partly deleted).

If the “SF” LED lights up and the “DIAG” LED flashes briefly three times and then flashes periodi-
cally three times. The firmware cannot be transferred to the internal memory of the FM (e.g. sy-
stem software on the memory card defective).

If the “DIAG” LED flashes five times cyclically and the “SF” LED goes out, the data transfer has been
completed 

 control “OFF”.

Leave the memory card inserted in the FM 357-2.

Switch the start-up switch of the FM 357-2 to position 1

Control “ON” 

 Wait until the control has booted with default values. After approx. 1 minute, the

“DIAG” LED flashes cyclically (3 Hz).

Control “OFF”

Switch the start-up switch of the FM 357-2 to position 0

Control “ON” 

 the control boots with the firmware

During booting of the FM 357-2, the licence on the memory card is checked with the version of the
firmware loaded onto the FM.

Installation of the firmware is described in Section 3.2 and start-up of the FM in Section 7.2 of the Ma-
nual.

Installing the configuring package on the programming device

The configuring package contains the parameterization tool, the standard function blocks, user exam-
ples, a preconfigured example interface for the OPs (irrelevant here) and NC-VAR-Selector (irrelevant
here).

Install the software in the following way:

Insert the CD-ROM in the CD drive of your programming device/PC.

Start the SETUP.EXE file on the CD-ROM.

Follow step by step the instructions displayed by the installation routine.

Select the following components in the dialog “FM 357-2 Toolset: Components”:

Parameterize FM 357-2

FM 357-2 Basic functions V3

The software is installed in the following directories when the defaults are accepted:

“Parameterize FM 357-2” parameterization tool: “[STEP7 directory]\S7FM357”

Function blocks FM 357-2: “[STEP7 directory]\S7LIBS/FM357_2L”

User examples FM 357-2: “[STEP7 directory]\EXAMPLES\zEn16_01”

Instructions on how to install the configuring package can also be found in Section 5.1 of the Manual.

– 3 –

Summary of Contents for SIMATIC FM 357-2

Page 1: ...SIMATIC FM 357Ć2 Getting Started First Steps in Commissioning Edition 03 2000 ...

Page 2: ... 3 1 of the Manual Connect up the power supply to the screw type terminal block on the FM 357 2 For more detailed wiring instructions please refer to Section 4 2 of the Manual Wire up the front connector The NC READY output must be connected into the EMERGENCY STOP circuit Insert the front connector in the FM 357 2 and lock For a description and connection instruc tions for front connector please ...

Page 3: ...control has booted with default values After approx 1 minute the DIAG LED flashes cyclically 3 Hz Control OFF Switch the start up switch of the FM 357 2 to position 0 Control ON the control boots with the firmware During booting of the FM 357 2 the licence on the memory card is checked with the version of the firmware loaded onto the FM Installation of the firmware is described in Section 3 2 and ...

Page 4: ...r project under SIMATIC 300 Station CPUxxx S7 Program When the message Do you want to replace the existing object and all its contents is displayed click on Yes Open the Sources directory and copy the STL source file fm357ob_n1 one FM 357 2 to the Sources directory of your project Open the Blocks directory and copy all the blocks it contains into the Blocks directory of your pro ject Open the copi...

Page 5: ...est Open the start up window by selecting Test Start up Click on the Test button Select operating mode Jog Make sure that Feed Stop is deselected and select Controller enable and Pulse enable Position the override pointer with the left mouse key to set the override to 50 Click on button R You can now start a traversing motion by pressing the spacer key As long as this key is pressed down your moto...

Page 6: ...nter the following markers in the Operand column DB115 dbx11 0 CTR_EN_AX3 Controller enable axis 3 DB115 dbx11 1 START Start of CPU axis 3 DB115 dbx11 5 ERR Error CPU axis 3 DB115 dbx11 6 INPOS CPU axis 3 position reached DB115 dbx11 7 ACTIV CPU axis active DB115 dbb10 ERR_NO in the case of an error error number of the CPU axis Establish the connection to the CPU via the menu Target System Establi...

Reviews: