SIMATIC
FM 357Ć2

Getting Started

First Steps in Commissioning

Edition 03/2000

Summary of Contents for SIMATIC FM 357-2

Page 1: ...SIMATIC FM 357Ć2 Getting Started First Steps in Commissioning Edition 03 2000 ...

Page 2: ... 3 1 of the Manual Connect up the power supply to the screw type terminal block on the FM 357 2 For more detailed wiring instructions please refer to Section 4 2 of the Manual Wire up the front connector The NC READY output must be connected into the EMERGENCY STOP circuit Insert the front connector in the FM 357 2 and lock For a description and connection instruc tions for front connector please ...

Page 3: ...control has booted with default values After approx 1 minute the DIAG LED flashes cyclically 3 Hz Control OFF Switch the start up switch of the FM 357 2 to position 0 Control ON the control boots with the firmware During booting of the FM 357 2 the licence on the memory card is checked with the version of the firmware loaded onto the FM Installation of the firmware is described in Section 3 2 and ...

Page 4: ...r project under SIMATIC 300 Station CPUxxx S7 Program When the message Do you want to replace the existing object and all its contents is displayed click on Yes Open the Sources directory and copy the STL source file fm357ob_n1 one FM 357 2 to the Sources directory of your project Open the Blocks directory and copy all the blocks it contains into the Blocks directory of your pro ject Open the copi...

Page 5: ...est Open the start up window by selecting Test Start up Click on the Test button Select operating mode Jog Make sure that Feed Stop is deselected and select Controller enable and Pulse enable Position the override pointer with the left mouse key to set the override to 50 Click on button R You can now start a traversing motion by pressing the spacer key As long as this key is pressed down your moto...

Page 6: ...nter the following markers in the Operand column DB115 dbx11 0 CTR_EN_AX3 Controller enable axis 3 DB115 dbx11 1 START Start of CPU axis 3 DB115 dbx11 5 ERR Error CPU axis 3 DB115 dbx11 6 INPOS CPU axis 3 position reached DB115 dbx11 7 ACTIV CPU axis active DB115 dbb10 ERR_NO in the case of an error error number of the CPU axis Establish the connection to the CPU via the menu Target System Establi...