6.4
Wiring rules
Cable cross-sections and ferrules
You can find information about this in section "Cable cross-sections and ferrules (Page 179)".
TWIN ferrules for wires of the push-in terminals
Due to the space required by TWIN ferrules with 0.75 mm
2
cross-section, you must ensure a
correct angle for the conductor arrangement when crimping the TWIN ferrule so that the wires
are optimally arranged.
D
E
①
Crimp TWIN ferrules in the correct angle
②
Cross-section of the terminal compartment
● a: 1.8 mm
● b: 2.4 mm
③
Spring release
Figure 6-5
TWIN ferrules
Permissible cable temperature
Read the information in section "Mechanical and climatic environmental conditions
Wiring
6.4 Wiring rules
ET 200SP HA Distributed I/O system
System Manual, 08/2019, A5E39261167-AD
85