12-2
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
12.1 Analog Input Module ET 200C; AI 4/8
12 Bit
(6ES7 144-0KH00-0XB0)
Technical Data
Transfer rates
9.6/19.2/93.75/187.5/
500/1500 kbaud
Bus protocol
DP standard
FREEZEable
yes
Galvanically isolated from
SINEC L2-DP bus
yes
Power loss
typ. 2 W
Weight
approx. 1050 g
Dimensions (W
H
D)
200
100
57
Diagnostics Functions
Voltage monitoring
green LED “RUN”
SINEC L2-DP bus
monitoring
red LED “BF”
Group diagnostics
red LED “DIA,
parameterizable
Supply Voltage Inputs and Internal Logic
Supply voltage (L+)
Nominal
24 V DC
Permissible range
20.4 ... 30.2 V
Value for t < 0.5 s
35 V
Current consumption from L+
Logic
80 mA
Inputs
Number of inputs
8 voltage inputs or
4 inputs for PT 100 or
8 inputs for
thermocouples
Galvanic isolation between
voltage supply and internal
logic
yes
Test voltage
500 V DC
Measured value ranges
Voltage sensor
"
80 mV,
"
250 mV,
"
500 mV,
"
1000 mV
Resistance sensor
0 ... 400
W
Permissible input voltage for
voltage input
max. 32 V
Inputs (Continued)
Characteristic linearization for the following
thermocouples
Types N, K, T, U, J, E
to IEC 584
Type L
to DIN 43710
Linearization accuracy in
nominal range
"
1
°
C
Signal generator connection
two-wire; four-wire for
Pt 100
Input resistance
>
1 MW
Measured value presentation
S5: 12 bit + sign
S7: 15 bit + sign
Overload range
approx. 17.5 %
Limit value alarm
yes, parameterizable for
channels 0 and 2
Diagnostics alarm
yes, parameterizable
Diagnostics information
accessible
yes
Temperature compensation
yes, parameterizable
Characteristic linearization
yes, parameterizable
Analog Modules
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...