![Siemens SIMATIC CPU 1515SP PC2 F User Manual Download Page 62](http://html.mh-extra.com/html/siemens/simatic-cpu-1515sp-pc2-f/simatic-cpu-1515sp-pc2-f_user-manual_1265335062.webp)
Maintenance
11.3 Restoring the delivery state
CPU 1515SP PC2 (F/T/TF)
Operating Instructions, 09/2018, A5E42603425-AA
61
Restoring the delivery state of the CPU 1515SP PC2 with restore USB stick
Before the restore
1.
Connect a monitor and a keyboard to the CPU.
2.
Switch off the power supply of the CPU.
3.
Remove all USB drives from the CPU.
4.
Connect the restore USB stick to a USB port.
5.
Switch on the power supply of the CPU.
→ The CPU is started.
6.
Press <Esc> to start the Boot Manager.
7.
Select the list entry for the USB stick in the Boot Manager.
8.
After the prompt, confirm the start by pressing any key.
→ The loading process is displayed (Windows logo).
→ The SIMATIC Restore men
u opens.
–
Select a language.
–
Select "CPU 1515SP PC2 (F/T/TF)" or "CPU 1515SP PC2 (F) + HMI".
–
Select the option "Completely restore system drive".
→ The original software is restored on Partition C:, Partition
D: is deleted.
After the restore
1.
Exit the Restore menu.
2.
Remove the restore USB stick.
3.
Proceed as described in Initial commissioning.
Further procedure
●
Re-connect any other required USB devices.
●
Transfer the license keys.