Diagnostics
3.2 Error types
2AO I HF analog electronic module (6ES7135-4MB02-0AB0)
16
Manual, 04/2007, A5E01076972-01
3.2
Error types
Analog output module error types
Table 3-1
Error types
Error type
Meaning
Remedy
16
D
10000: Parameter assignment
error
Module cannot use the
parameter for the
channel:
Inserted module does not
match the one
configured.
Incorrect parameter
assignment.
Correct the configuration
(align actual and set
configuration).
Correct the parameter
assignment (wire break
diagnostics only
parameterized for the
permitted measuring
ranges).
9
D
01001: Error
Internal module error has
occurred (diagnostic
message on channel 0
applies to the entire
module).
Replace the module.
6
D
00110: Open circuit
Line to the final
controlling element
interrupted.
Correct the process wiring.