Properties
1.1 2AO I HF analog electronic module (6ES7135-4MB02-0AB0)
2AO I HF analog electronic module (6ES7135-4MB02-0AB0)
10
Manual, 04/2007, A5E01076972-01
Suppression of interference, limits of error
Crosstalk between the outputs
< -60 dB
Operational limit (in the entire temperature range,
with reference to the output range)
± 0,1 %
Basic error limit (operational limit at 25°C with
reference to output range)
± 0,05 %
Temperature error (with reference to the output
range)
±0.003%/K
Linearity error (with reference to the output range) ±0.01% (for resistive load)
Repeatability
(in steady state at 25°C with reference to output
range)
± 0,01 %
Transmitter selection data
Output range (rated value)
± 20 mA
4 mA to 20 mA
Load impedance (in the rated range of the output)
•
For current outputs
•
For inductive load
Max. 500 Ω
1 mH
Current output
•
Open circuit voltage
18 V
Destruction limit against voltages/currents applied
from outside
•
Voltage at the outputs to M
ANA
Max. 15 V continuous; 75 V for max. 1 ms
(sampling ratio 1:20)
•
Current
Max. 50 mA DC
Connection of actuators
•
Current output two-wire connection
Supported