10 Programming of control facilities
Resistance
in ohms
Monitoring current in mA
Remark
Load
Monitoring input
Transponder-
output ST
Voltage and current in case of control
* with UB= 24V
40 – 95
50
Output voltage=UB Current 0,26-0,6A*
90 – 250
20
Output voltage =UB Current 0,096-0,266A*
250 – 550
8
Output voltage =UB Current 43mA-96mA*
500-1000
4
Output voltage =UB Current 24mA-48mA*
950-2400
2
Output voltage =UB Current 10mA-25mA*
2000-4000
1
Output voltage =UB Current 6mA-12mA*
300 – 700
6
Output voltage 20V Current 40mA-66mA
500 – 1000
4
Output voltage 20V Current 25mA-40mA
900 – 2000
2
Output voltage 20V Current 10mA-28mA
2000 – 5000
1
Output voltage 20V Current 4mA-10mA
0
0
No fault monitoring
Table 24: Monitored control lines
The maximum line resistance must not exceed 10 % of the load resistance.
10.1.5 Display (ANZ)
The actuators in the Display category serve as indicators for the status of detectors, detector
zones or outputs
Display is mainly used for programming detector outputs when connecting detector shunt dis-
plays and for the indicator panel control facility SPF 3200.
The source (e. g. detector objects, alarm zones, detector zones, detectors or actuator statu-
ses) that tripped a display can be established for every facility. Operators can also choose
from a number of different control patterns. It is thus possible to vary the signalling criteria
(alarm, prewarning, prealarm, fault, signal) and the activation form (static, flashing or dy-
namic).
Displays cannot be activated by command. Displays cannot be tripped in operating panel
lists.
10.1.6 Close-and-retain system (FSA) control facility and fire section control facility
FSA
The FSA control facility is an inverse-operated output that is released in the event of a fault. It
is released in the event of an alarm, signal, fault, inspection, disablement of the activating de-
tector. It is also command-driven. The close-and-retain equipment is connected via the con-
trol module SPF 5100 to a detector output of a SIGMASYS detector.
The control module requires and external power supply unit.
Fire section control facility
Tripped in the event of an alarm (including an initial alarm), signal, fault, prealarm, source di-
sablement, output disablement. It is manually activated.
10.1.7 Detector display and event display control pattern
Actuators of this type can only be tripped by sources that are connected to the same module.
64 / 128
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Summary of Contents for SIGMASYS C
Page 4: ......
Page 30: ......
Page 38: ......
Page 44: ...6 Functions 36 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 48: ......
Page 62: ......
Page 84: ......
Page 110: ......
Page 128: ...16 Appendix 120 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 130: ......
Page 132: ......
Page 134: ......
Page 137: ......