42
SICAM T 7KG966, Product Information
E50417-B1050-C493-A4, Edition 12.2012
Bus protocol IEC 60870-5-103
Baud rate
9600 bit/s
19 200 bit/s
38 400 bit/s
Measured values range
120 %
240 %
Protocol
half-duplex
Max. cable length
1000 m
17.7 Supply Voltage
Rated input voltages
AC 110 V to 230 V or
DC 24 V to 250 V
Frequency at AC
45 Hz to 65 Hz
Admissible input voltage
±20 %
tolerance (applies to all input
voltages)
Admissible higher harmonics 2 kHz
at AC 115 V or AC 230 V
Maximum power consumption 5 W/16 VA
17.8 Battery
Types
PANASONIC CR2032
VARTA 6032 101 501
Voltage
3 V
Capacity
230 mAh
Typical life time
at permanently available
power supply
10 years
at not permanently available
power supply
2 month within
10 years