
Operation and Display
4.3 Key Definition
SICAM P37, 3-phase Harmonic Power Meter, User Manual
E50417-H8940-C563-
4
, Release Date
06.2018
31
Note
Password level (1 bit, 0 to 2) and password (6 bits) should be entered at first for key setting. Password level
and permission:
• L0 password-all parameters above are configurable;
• L1 password-all parameters above are configurable;
• L2 password-all parameters except for meter reset, clearing extreme value and PT/CT conversion ratio are
configurable. All default password is 000000.
Note
The meter should be reset after altering PT/CT ratio to ensure reasonable correspondence between
communication reading and displayed metering data.
3. Parameter setting with keys (take "Conn communication setting" for example)
Figure 4-2
Parameter setting with keys
5
Display
setting
Time of returning to
cyclic display state
when no operation
1 ... 99
Unit: min.
Default setting: 10
Time of backlight
on when no opera-
tion (normally on
when set to 0)
0 ... 99
Unit: min.
Default setting: 10
Interval of cyclic
display
1 ... 99
Unit: sec
Default setting: 5
NO.
1
st
level menu
2
nd
level menu
Symbol
Definition
Symbol
Definition
Range
Remarks