Communication
6.2.4 Information mapping table
SICAM P20 P21 P22, 3-phase Current Power Meter, User Manual
E50417-H8940-C558-
4
, Release Date
06.2018
33
Note
High bytes BIT0-BIT3 respectively mean status of binary input 1-2. Bit value 0 means input is open while 1
means input is closed.
Low bytes BIT0 and BIT1 respectively mean status of relay output 1. Bit value 0 means contact is open (relay
no operation) while 1 means contact is closed (relay closed).
Other Parameters
Alarm 1
Limit viola-
tion data type
0110 H
unsigned int
2 bytes
R/W
0...31
See alarm type table
High 16 bits
of Limit viola-
tion threshold
0111 H
unsigned long
4 bytes
R/W
Arbitrary
value
Threshold=set val-
ue/100
Low 16 bits
of Limit viola-
tion threshold
0112 H
Limit viola-
tion detection
type
0113 H
unsigned int
2 bytes
R/W
0...1
0: over, 1: below
Alarm port
0114 H
unsigned int
2 bytes
R/W
0...1
0: off
1: alarm output to relay
output 1
Alarm 2
0115 H
...0119 H
10 bytes
R/W
See Alarm 1
Alarm 3
011A H
...011E H
10 bytes
R/W
See Alarm 1
Alarm 4
011F H
...0123 H
10 bytes
R/W
See Alarm 1
Alarm 5
0124 H
...0128 H
10 bytes
R/W
See Alarm 1
Alarm 6
0129 H
...012D H
10 bytes
R/W
See Alarm 1
Parameter Address
Data
Type
Length
R/W
Data
Range
Remark
Parameter Address
Data
Type
Length
R/W
Data
Range
Remark
Cyclic display time
0132 H
unsigned int
2 bytes
R/W
1...99
Unit: sec
Number of cyclic
display items
0133 H
unsigned int
2 bytes
R/W
0...0xFF
See description of
cyclic display parame-
ters
1
st
screen of cyclic
display item of
screen A
0140 H
unsigned int
2 bytes
R/W
0...999
See cyclic display code
table of area A
Number n screen
of cyclic display
item of screen A
...
unsigned int
2 bytes
R/W
0...999
16
th
screen of
cyclic display item
of screen A
014F H
unsigned int
2 bytes
R/W
0...999