Operation and Display
4.3 Key Definition
SICAM P20 P21 P22, 3-phase Current Power Meter, User Manual
E50417-H8940-C558-
4
, Release Date
06.2018
19
Key Setting Parameters
1. Key functions at parameter setting mode
2. Data items configurable with key
Key symbol
▲
▼
Function
a) "
▲
" to switch digit or flip over;
b) "
▼
" to move cursor or flip over.
Enter next menu
a) Press "
" and "
" at the same time to enter
setting screen.
b) Press "
" to enter next menu or "confirm" parameter
setting.
c) Press "
" to return to previous menu or "cancel" pa-
rameter setting
1
.
1
.Press "
" once after adjusting parameters with "
▲
" and "
▼
" to display "Sure", and press "
" once
again to alter parameters. Pressing "
" immediately after "Sure" appears will cancel current alteration.
NO.
1
st
level menu
2
nd
level menu
Symbol
Definition
Symbol
Definition
Range
Remarks
1
Communi-
cation
setting
Baud rate
600 ... 38400
Default setting:
2400
Parity
8E1/8o1/8n1/8n
2
Default setting: 8E1
Modbus address
0 ... 247
Default setting: 0
Modbus sending
delay
0 ... 2999
Default setting: 10
DL/T645 high 6
address
0 ... 999999
Default setting: 0
DL/T645 low 6
address
0 ... 999999
Default setting:
Last 3 digital of S/N
2
Ratio
setting
Current conversion
ratio integer part
0 ... 9999
Combination 0 ...
9999.9999
Current conversion
ratio decimal part
0 ... 9999
Default setting: 1
3
System
setting
Connection
3P4L
3P3L_2CT
3P3L_3CT
AUto
3phase4wire
3phase3wire -2CT
3phase3wire -3CT
Automatic
Password
6 bits in total, alter-
ing L0-2 password
Default setting:
000000