![Siemens SICAM A8000 Series Manual Download Page 27](http://html.mh-extra.com/html/siemens/sicam-a8000-series/sicam-a8000-series_manual_377373027.webp)
Standard I/O Modules
SICAM A8000 Series, SICAM I/O Modules
Unrestricted
27
DC8-012-2.06, Edition 09.2019
2.2.3
Technical Data
Binary Inputs
16 binary inputs
•
2 groups, 8 inputs each
•
Galvanic insulation
•
Each group has a common return of selectable polarity
Filter time
3 ms
1)
Nominal voltages
DC 48/60 V
Operating points
≤
24 V
logical "0"
≥
36 V
logical "1"
Input circuits
DC 36…78 V
The circuits are operated by means of an external voltage
Rated current
0.5…2.5 mA
at 36…78 V
Power Supply
Operating voltage
DC 4.75…5.5 V
130 mW
The voltage is picked off at the system bus
Mechanics and Connectors
Terminals
Removable screw terminals (grid size 5.08)
Rated impulse voltage
4 kV (category III / AC 230 V)
Connection data X1, X2
Locking torque
2)
(PHOENIX)
(FCI)
0.5 Nm to 0.6 Nm
0.36 Nm to 0.44 Nm
AWG
min. 22
max. 12
Conductor cross section solid
min. 0.33 mm²
max. 2.5 mm²
Conductor cross section stranded
min. 0.33 mm²
max. 2.5 mm²
Conductor cross section stranded with
ferrule without plastic sleeve
min. 0.33 mm²
max. 2.5 mm²
Conductor cross section stranded with
ferrule with plastic sleeve
min. 0.33 mm²
max. 2.5 mm²
2 wires stranded with ferrule without
plastic sleeve
min. 0.33 mm²
max. 1 mm²
2 wires stranded with TWIN ferrule with
plastic sleeve
min. 0.5 mm²
max. 1.31 mm²
Wire strip length
min. 6 mm
max. 7 mm
Length ferrule
10 mm
Dimensions
124 x 30 x 132 mm (L x W x H, dimensions w/o DIN rail)
Weight
Approx. 249 g (inkl. bus module 12 g)
1)
if the sensor voltage of a group of binary inputs is monitored for failures (parameter
SVM_monitoring
), there is a dedicated binary input for each group (IN D07 and IN D17), this input
has a filter time of 2 ms
2)
the respective manufacturer is imprinted at the terminal (see section
Note
Above an input voltage of 60 V and above an ambient temperature of +65°C (horizontal mounting) / +45°C
(vertical mounting) a derating occurs. In this case, only a maximum of 13 inputs may be operated
simultaneously.