Siemens SFPO-11 Installation Instructions Manual Download Page 3

Siemens Building Technologies
Fire Safety

P/N 315-033290C-7

3

To Install Detector Head:

• Align LED in detector with LED symbol on base and

insert detector into base.

• Rotate detector counterclockwise while gently press-

ing on it until the detector seats fully into base.

• Then rotate the detector clockwise until it stops and

locks in place. Insert optional locking screw (Order
Model LK-11).

To Remove Detector Head:

• Loosen locking screw, if installed. Then rotate the

detector counterclockwise until stop is reached.

• Pull detector out of base.

DETECTOR TESTING

Only qualified service personnel should test. To assure proper
operation of the detector and control panel, both the Sensitivity
and Functional Test should be conducted. The minimum test
schedule may be found in the current edition of NFPA 72 for
installations in the U.S., and CAN/ULC-S537, The Verification of
Fire Alarm Systems, for installations in Canada.

Sensitivity Measurement

The sensitivity of SFPO-11 and SFP-11 detectors can be tested
individually using the SDPU. Refer to the SDPU Manual, P/N
315-033260C.

Functional Test

Perform a functional (Go, No-Go) test by activating the detec-
tor using

 

Test Gas, P/N 315-282747, following the instruction

on the label. This test is simply used to ensure that smoke
can enter the sensing chamber and alarm the control panel
when the detector reaches the programmed obscuration (con-
centration) level.

The SFPO-11/SFP-11/SFPT-11 detectors can also be tested
individually using the SDPU. Refer to the SDPU Manual, P/N
315-033260C.

TO INITIATING
CIRCUIT OF
SIEMENS BUILDING
TECHNOLOGIES, INC.
COMPATIBLE
CONTROL UNIT

OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
RL-HW / RL-HC

TO NEXT BASE

TO NEXT BASE

DO NOT
USE AN
END OF
LINE
DEVICE

DETECTOR BASE
MODEL DB-11

LINE 1**

LINE 2**

5

6

1a

TB1

TB3

TB2

1b

5

6

1a

1b

RELAY*
CONTACTS
3A, 120 VAC
3A, 30 VDC

REMOTE RELAY
BASE MODEL DB-SR

*The relay contacts are shown after System reset, which represents the non-alarm condition.

**SFP-11/SFPT-11/SFPO-11 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.

5+

NO

C

NC

6

5+

NO

C

NC

6

DO NOT
USE AN
END OF
LINE
DEVICE

Figure 3
Installation and Wiring Diagram

DETECTOR CLEANING AND MAINTENANCE

The control unit automatically indicates the trouble mes-
sage "Maint Alert" for any detector whose smoke chamber
changes to the level where the set sensitivity cannot be
maintained. In such circumstances, the detector may re-
quire cleaning as a result of dust or debris accumulation;
follow the 

CLEANING PROCEDURE

 steps.

The recommended requirement for detector maintenance
consists of the annual cleaning of dust and debris from the
detector head. Cleaning program intervals should be geared
to the individual detector environment.

If the fire alarm control panel is connected to a
Fire Department, etc., or activates an external
system (fire extinguishing, etc.), disarm the
appropriate outputs before servicing to
prevent activation. Be sure to reset and
rearm the system at completion of servicing.
Notify facility personnel that the system is
being serviced so that any alarm soundings
can be ignored during the period of service.

CLEANING PROCEDURE*

(See Figures 4 and 5)

1. Notify the proper personnel that the fire alarm system

is being serviced.

2. Remove the detector to be cleaned from its base. (See

To Remove Detector Head

 on page 3.)

3. Using a small blade screwdriver, remove the cover from

the rest of the detector by releasing the 2 cover tabs
located on the outside of the cover. Separate the foam
screen from the cover.

4. Remove the labyrinth from the sensing chamber by

squeezing the labyrinth sides along the release axis and
pulling out. Carefully remove the labyrinth/thermal holder
assembly being sure not to damage or disconnect the
thermal wires.

* Model SFPT-11 is not field cleanable.

Summary of Contents for SFPO-11

Page 1: ...f smoke or aerosol for an extended period of time the detector is programmed to make the safe decision and sig nal an alarm condition Because the amplitude and duration of deceptive phenomena are unbounded the rule of thumb is to keep detectors as far as practical from sources that can produce an unusually large quantity of smoke for about a minute This effort during placement of detectors within ...

Page 2: ...irements in NFPA 72 Chapter 5 for High Air Movement Areas and Control of Smoke Spread When installing Model SFPO 11 and SFP 11 in existing installa tions with an existing duct detector housing order an AD 11UK Air Duct Upgrade Kit DA 304 P N 500 695967 and use it in that installation This kit includes the required housing cover P N 305 095676 Do not use Model SFPO 11 and SFP 11 with any other air ...

Page 3: ...b RELAY CONTACTS 3A 120 VAC 3A 30 VDC REMOTE RELAY BASE MODEL DB SR The relay contacts are shown after System reset which represents the non alarm condition SFP 11 SFPT 11 SFPO 11 is a polarity insensitive detector Line 1 and Line 2 can be either line of the loop 5 NO C NC 6 5 NO C NC 6 DO NOT USE AN END OF LINE DEVICE Figure 3 Installation and Wiring Diagram DETECTOR CLEANING AND MAINTENANCE The ...

Page 4: ...se 7 Test the detector See Detector Testing section of this instruction 8 When all service has been completed notify personnel See Step 1 that system service has been completed No field repair of the detectors should be attempted The detectors are factory repair able only ELECTRICAL RATINGS CX 2 FDLC Addressable Device Loop ratings Voltage 18 31V pulsing Current 1mA Figure 4 Disassembling of SFP 1...

Reviews: