Appendix
A.2 Operating conditions
216
Manual, 08/2017, L1V30368969104A-02
A.2
Operating conditions
A.2.1
Temperature
●
At a temperature of -20 °C to +40 °C without derating
●
At temperatures from - 20 °C to +70 °C, the derating correction factor K
t
must be factored
in
K
t
– correction factor
Temperature
0.9
40 °C to 50 °C
0.8
50 °C to 60 °C
0.7
60 °C to 70 °C
The simplified method of calculating the derating is used here:
l
thu
≤ I
th
x K
f
In a few cases, specific requirements demand precise derating calculations. Contact
Siemens for this.
A.2.2
Humidity
●
At 80 % air humidity and 55 °C, condensation does not take place
●
At 95 % air humidity and 40 °C, condensation does not take place
A.2.3
Altitude conditions
●
Up to 2000 m no derating
●
For higher altitudes, the following derating correction factor must be factored in
K
a
– correction factor
2000 m < A
≤
3000 m
3000 m < A
≤
4000 m
U
e
0.95
0.8
I
e
0.85
0.85
Summary of Contents for SENTRON
Page 1: ......
Page 2: ......
Page 10: ...Introduction 10 Manual 08 2017 L1V30368969104A 02 ...
Page 12: ...General information 2 1 Certification 12 Manual 08 2017 L1V30368969104A 02 ...
Page 24: ...Product information 3 2 Product family 24 Manual 08 2017 L1V30368969104A 02 ...
Page 26: ...Functions 26 Manual 08 2017 L1V30368969104A 02 ...
Page 176: ...Accessories 9 18 Electronic module 3KC8 only 176 Manual 08 2017 L1V30368969104A 02 ...
Page 220: ...Appendix A 3 Storage conditions 220 Manual 08 2017 L1V30368969104A 02 ...