73
Code Command
Designation on the
ATC
Required
password
Description
C18 Reset alarms A03 - A04
RESET A03/04
Advanced Restores the opening or closing command of
the switching devices after generating the
alarms A03 - A04
C19 Simulates priority source fail-
ure
FAIL.SIMULATION Advanced The device switches to test mode and simu-
lates failure of the priority source for two
minutes.
After this, it executes a load transfer as pro-
grammed (see chapter Simulation of priority
source failure (Page 69)).
5.1.9.3
Event log
In the event log of the ATC6500 you can view the last 250 events. The event log is accessed
by:
●
Selection of the Event Log symbol
●
Scrolling through the display pages
The event log shows:
●
Number of the event
●
Error code
●
Date / time and a brief description of the event