51
Figure 10: Typical control schematic for stored-energy operator
52a and 52b spare contacts (standard)
52a and 52b spare contacts (optional)
AC power
supply
DC power
supply
Protective
relays
Legend
01/C
Control switch close (remote)
01/T
Control switch trip (remote)
08
Close and trip power disconnect
08M
Motor power disconnect
52a
Auxiliary switch, open when circuit
breaker is open
52b
Auxiliary switch, closed when
circuit breaker is open
52SRC
Closing spring release coil
52T
Opening spring release coil
52Y
Anti-pump relay
69
Closing cutout switch
88
Spring charge motor
G
Green indicating light (remote)
R
Red indicating light (remote)
LS3
Closing spring position switch, closed
when closing spring is discharged
LS9
Closing spring position switch, open
when closing spring is discharged
LS21
Motor cutoff switch, closed when
closing spring is discharged
LS22
Motor cutoff switch, closed when
closing spring is discharged
LS41
Closing spring position switch, open
open when closing spring is discharged
W
White indicating light (remote)
XO
Plug connector (operator
connections)
Schematic shown with closing
springs discharged and circuit
breaker open.
Summary of Contents for SDV7-AR
Page 54: ...54 Table 16 Remarks ...