27
Technical data
Table 6: Minimum trip
currents
Characteristic
Unit
Voltage class
Rated maximum voltage U
r
kV
15.5
27.0
27.0
38.0
Rated continuous current I
r
A
630, 800
630, 800
630, 800
630, 800
Rated lightning impulse withstand voltage U
p
kV
110
125
150
170
Power frequency insulation level withstand test
voltage (one minute dry) U
d
kV
50
60
70
70
Rated symmetrical interrupting current I
sc
kA
12.5, 16
12.5
12.5, 16
12.5, 16
Rated asymmetrical making current (rms)
kA
20, 25
20
20, 25
20, 25
Rated peak making current
kA
32.5, 41
32.5
32.5, 41
32.5, 41
Mechanical life (operating cycles)
OPS
10,000
10,000
10,000
10,000
Permissible short-circuit operations
OPS
up to 250
up to 250
up to 250
up to 250
Ambient temperature range
ºC
-40 to +55
-40 to +55
-40 to +55
-40 to +55
Centerline spacing between phases
in
(mm)
14.8 (376)
14.8 (376)
14.8 (376)
14.8 (376)
Flashover distance
Unit
Phase/phase
in
(mm)
12.3 (312)
12.3 (312)
12.3 (312)
12.3 (312)
Phase/ground (earth)
in
(mm)
10.4 (265)
10.4 (265)
13.4 (340)
13.4 (340)
Creepage distance
Unit
Phase/ground (earth)
in
(mm)
31.9 (810)
31.9 (810)
50.8 (1,290)
50.8 (1,290)
Between line-side and load-side terminal
in
(mm)
46.1 (1,170)
46.1 (1,170)
54.8 (1,390)
54.8 (1,390)
Table 5: Main
characteristic data
Protective function
Unit
Minimum trip current
Phase faults
A
40
40
40
40
Ground (earth) faults
A
4
4
4
4
Sensitive ground (earth) faults
A
4
4
4
4
Table 7: Operating
times
Operation time
Unit
Time
Closing time
ms
<60
<60
<60
<60
Opening time
ms
<35
< 35
< 35
< 35
Arcing time
ms
<15
<15
<15
<15
Interrupting time
ms
<50
<50
<50
<50
Table 8: Dead times for
recloser cycle
(reclosing interval)
Dead time
Unit
Time range
Dead time after first open
s
0.2 to 14,400
0.2 to 14,400
0.2 to 14,400
0.2 to 14,400
Dead time after second and third open
s
2 to 14,400
2 to 14,400
3 to 14,400
3 to 14,400
Dead time after fourth open
s
30 to 14,400
30 to 14,400
30 to 14,400
30 to 14,400