Safety notes
SCALANCE X-300M PoE
10
Compact Operating Instructions, 05/2016, A5E02630810-09
General information
WARNING
Safety extra low voltage
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a
Limited Power Source (LPS).
This means that only SELV / LPS (Limited Power Source) complying with IEC 60950-1 / EN
60950-1 / VDE 0805-1 must be connected to the power supply terminals. The power supply
unit for the equipment power supply must comply with NEC Class 2, as described by the
National Electrical Code (r) (ANSI / NFPA 70).
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
A power source that supplies safety extra low voltage combined with a following NEC Class
2 power limiter also meets the requirements according to IEC 60950-1 / EN 60950-1 / VDE
0805-1 or NEC Class 2. A suitable power limiter is for example the redundancy module
SITOP PSE202U NEC Class 2 (article number 6EP1962-2BA00).
WARNING
Opening the device
DO NOT OPEN WHEN ENERGIZED.
General notices about use in hazardous areas
WARNING
Risk of explosion when connecting or disconnecting the device
EXPLOSION HAZARD
DO NOT CONNECT OR DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR
COMBUSTIBLE ATMOSPHERE IS PRESENT.
WARNING
Replacing components
EXPLOSION HAZARD
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION
2 OR ZONE 2.
WARNING
Requirements for the cabinet/enclosure
When used in hazardous environments corresponding to Class I, Division 2 or Class I,
Zone 2, the device must be installed in a cabinet or a suitable enclosure.