Connection
6.2 Power supply
SCALANCE W774-1 / W734-1
50
Operating Instructions, 03/2022, C79000-G8976-C325-15
6.2
Power supply
Note
Galvanic isolation of the power supply unit
To ensure dielectric strength according to IEEE 802.3, the supplying 24 V power supply
unit must be galvanically isolated with a dielectric strength of 1500 VAC. The galvanic
isolation must also not be bridged by other devices connected to the same power supply
unit.
SCALANCE W774/W734 RJ45
With this device version, there are two options for the power supply:
•
Direct infeed via the four-pin connection socket
①
For the direct infeed of the power supply, use copper cables with the following
properties:
–
Round cable cross-section with 6 to 8 mm diameter.
–
Two-wire cable with 0.5 to 1.5 mm2 cross-section per wire.
–
Permitted tensile load at least 100 N. - UL
–
Listing of the cables according to the national installation regulations. In areas
where NEC or CEC applies: Type PTLC or ITC
•
Power over Ethernet via the RJ45 Ethernet interface P2
②
. The other Ethernet
interface P1 is not capable of PoE.