background image

1. Polarity shown in active state at terminals 1 and 2 of SBGA-34 and 1+, 1-, 2+ and 2-

of FC-901 NAC circuits. Proper polarity must be maintained or audible base will not
operate properly. Each audible base must be tested to verify operation.

2. Tone selection (refer to page 7 for more information).
3. SBGA-34 terminals 5-8 are polarity insensitive. Line 1 and Line 2 can be either line

of the loop.

4. SBGA-34 shown Style Z (Class A). It may also be wired as Style Y (Class B).
5. FC901 Notification Appliance outputs that can be configured for Class B or Class A.

Refer to the FC-901 Operation, Installation and Maintenance Manual, P/N 315-
XXXXXX, as applicable, to set jumpers JP1-4 for Class A or Class B operation.

SBGA-34

SBGA-34

-

+

-

+

8

8

7

7

6

6

5

5

1

1

2

2

3

3

4

4

TO NEXT

ADDRESSABLE

DEVICE

LINE 1

LINE 2

LINE 1

LINE 2

FROM P2

OF FC-901 PANEL

NOTE 2

NOTE 2

NOTE 3

NOTE 3

N

_B

N

N

_B

P

N

_A

N

N

_A

P

Figure 6
Installation/Wiring Diagram for SBGA-34 Audible connected to FC901 Panel

1. Polarity shown in active state at terminals 1 and 2 of SBGA-34 and 1+, 1-, 2+ and 2-

of FC2025/2050 FC922/924 NAC circuits. Proper polarity must be maintained or
audible base will not operate properly. Each audible base must be tested to verify
operation.

2. Tone selection (refer to page 7 for more information).
3. SBGA-34 terminals 5-8 are polarity insensitive. Line 1 and Line 2 can be either line

of the loop.

4. SBGA-34 shown Style Z (Class A). It may also be wired as Style Y (Class B).
5. FC2025/2050 FC922/924 Notification Appliance outputs that can be configured for

Class B or Class A. Refer to the FC2025/2050 Operation, Installation and
Maintenance Manual, P/N A6V10337045, or the FC922/924 Installation Instructions,
P/N A6V10356958, as applicable, to set jumpers JP1-4 for Class A or Class B
operation.

SBGA-34

SBGA-34

-

+

-

+

8

8

7

7

6

6

5

5

1

1

2

2

3

3

4

4

TO NEXT

ADDRESSABLE

DEVICE

LINE 1

LINE 2

LINE 1

LINE 2

FROM P2

OF FC2025/2050

FC922/924

NOTE 2

NOTE 2

NOTE 3

NOTE 3

N

A

C

1-

2

N

A

C

1-

2

N

A

C

1-

1

N

A

C

1-

1

1

2

3

4

+

+

-

-

Figure 7
Installation/Wiring Diagram for SBGA-34 Audible to FS20 Panel

Summary of Contents for SBGA-34

Page 1: ...35 AE 30U 24 VDC BATTERY PS 35 POWER INPUT 120 VAC 50 60 Hz CONNECTED TO GROUND REFERENCE OF THE PANELS IT S CONNECTED TO REFER TO TABLE X FOR GROUND CONNECTION LINE 2 LINE 1 LINE 1 LINE 2 LINE 2 LINE 1 FOR CONNECTION TO SLC LOOP FROM DLC LOOP OF SYSTEM OR FS DLC LOOP OF FS 250 SYSTEM FIREFINDER XLS TO NEXT SBGA 34 DB3S DB X3RS OR DB 11 4 4 4 4 8 8 12 PIN PLUG 5 5 5 5 9 6 6 6 6 10 3 3 3 3 7 7 2 2 ...

Page 2: ...E 3 NOTE 3 Figure 2 Installation Wiring Diagram for SBGA 34 Audible Powered by ZIC 4A FireFinder XLS System 1 Polarity shown in active state at terminals 1 and 2 of SBGA 34 and 1 4 of ZIC 8B Proper polarity must be maintained or audible base will not operate properly Each audible base must be tested to verify operation 2 Tone selection refer to page 7 for more information 3 SBGA 34 terminals 5 8 a...

Page 3: ...4 5 6 1b 1a 8 8 7 7 6 6 5 5 1 1 2 2 3 3 4 4 TO NEXT ADDRESSABLE DEVICE LINE 1 LINE 2 LINE 1 LINE 2 24K 1 2W 5 FROM FS DLC OR FDLC LOOP OF FS 250 OR FS 250C SYSTEM NOTE 2 NOTE 2 NOTE 3 NOTE 3 TB12 TB13 4 3 4 3 2 1 2 1 TB8 TB7 NO NC C NC NO C Figure 4 Installation Wiring Diagram for SBGA 34 Audible Powered by NAC Circuits FS 250 FS 250C Systems and MPC6000 MPC7000 SBGA 34 SBGA 34 5 6 1b 1a 8 8 7 7 6...

Page 4: ... for SBGA 34 Audible connected to FC901 Panel 1 Polarity shown in active state at terminals 1 and 2 of SBGA 34 and 1 1 2 and 2 of FC2025 2050 FC922 924 NAC circuits Proper polarity must be maintained or audible base will not operate properly Each audible base must be tested to verify operation 2 Tone selection refer to page 7 for more information 3 SBGA 34 terminals 5 8 are polarity insensitive Li...

Page 5: ...ctor is connected This must be included in the determining the battery size of the panel 2 SBGA 34 alarm current is drawn both from external power supply source and the detector loop in which their associated detector is connected Care must be taken to verify that this is properly entered during its battery calculation requirements 3 SBGA 34 audible section can be energized by an auxiliary power s...

Page 6: ...minimum of 14 AWG must be used 9 Even though no specific spacing is allocated to the detectors used with this base refer to NFPA Standard 72 National Fire Alarm Code and the installation instructions of the detector being used see Table 1 For additional information on the used in an individual system refer to the installation instructions for that particular module or contact your authorized Sieme...

Page 7: ...NEXT SBGA 34 DB 11 DB 3S or DB X3RS POWER SUPPLY POLARITY SHOWN IN ACTIVE STATE _ SBGA 34 4 3 2 1 JUMPER FOR TONE SELECTION LINE 1 LINE 2 LINE 1 LINE 2 FROM P2 LOOP NOTE Use both Terminals or leads for connection break wire run to provide electrical supervision Figure 8 SBGA 34 Audible Base Terminal Blocks TONE SELECTION With audible base Model SBGA 34 the user can choose either temporal tone Temp...

Page 8: ...udible Base Model SBGA 34 attaches only to a 4 inch square electrical box with extension Mounting the Base 1 Route all wires out from the outlet box 2 Make connections directly to the audible base terminals located on the back of the base Refer to the related Installation Wiring Diagram 3 After all bases are installed check loop continuity For SBGA 34 Detector loop continuity check refer to the DP...

Reviews: