Risk of electrical shock 

z

 

Ensure that the connection is secure and the circuit 
breaker to the supply circuit is easily accessible when 
operating the unit (e.g. fuse up to 16 A). 

z

 

Do not connect any external consumers to the fuse. 

z

 

Grounding has to adhere to the respective safety 
regulations. 

Device damage due to overvoltage 

z

 

Connect the unit only to current sources with the 
specified voltage. Information on the power supply is 
available on the power supply unit / rating plate.  

Risk of panic reactions 

z

 

Prior to testing the system, make sure all important 
persons involved and supporting authorities are 
informed. 

z

 

To avoid panic, all involved should be informed prior to 
testing alarm facilities. 

Danger of explosion 

z

 

Make sure that the battery poles do not short circuit. 

z

 

Please pay attention to battery polarity. 

z

 

Always fasten the battery in place with the holder 
intended for this purpose. 

 

 

Technical data 

Mains voltage 

230 V AC, + 10 %  / -15 %, 50 Hz 

Power intake 

max. 34 VA (at 230 V AC) 

Mains supply fuse  

160 mA T (Mains power) 

Output voltage/current 

13.7 V DC / 1.3 A  

Max. ripple at 1.3 A  

60 mV  

Relay, single-pole 
changeover  

48 V / 5 A  

Battery type according to 
VdS 

YUASA, Type NP7-12 
(12 V / 7.2 Ah) recommended 

Battery type not according 
to VdS 

YUASA, Type NP17-12 
(12 V / 17 Ah) recommended 

Operating temperature  

0 to 40 °C  

Steel housing  

1.5 mm  

Dimensions (W x H x D) 

303 x 400 x 87.5 mm 

Protection rating 

IP30  

Environmental class  

II  

Weight without battery  

5.5 kg  

 

 

 

Package contents 

The SAP 14 package contains the following:  

z

 

One SAP14 power supply unit 

z

 

One battery holder 

z

 

One set (4 units) of spacers 

z

 

Installation instructions (de, en, fr, it) 

z

 

Terminal connection diagram 

Summary of Contents for SAP14

Page 1: ...pecific safety standards or regulations for project planning operating and dispo sing of the product z The device is always to be disconnected from the mains or battery prior to performing maintenance work or installing additional devices Liability claim z Do not connect the device if components are missing or damaged z Only make changes to the unit that are explicitly mentioned in this document o...

Page 2: ...lities Danger of explosion z Make sure that the battery poles do not short circuit z Please pay attention to battery polarity z Always fasten the battery in place with the holder intended for this purpose Technical data Mains voltage 230 V AC 10 15 50 Hz Power intake max 34 VA at 230 V AC Mains supply fuse 160 mA T Mains power Output voltage current 13 7 V DC 1 3 A Max ripple at 1 3 A 60 mV Relay ...

Page 3: ... 3 Fig 1 2 Remove cover 1 2 4 5 6 7 10 3 8 9 R45 F1 B4 F2 1 F3 3 F4 4 F5 6 Fig 2 Power supply assembly circuit board SMP14 1 LED flashes when E bus communication is intact 2 Address button 3 Not used 4 E Bus connection to burglary detection control unit B1 B2 B3 B4 B4 is secured by F1 5 4 outputs 12 V 1 3 4 6 which are each secured with a fuse F2 to F5 6 Output for mains supply indication not fuse...

Page 4: ...y 1 5 cm proud B Fig 3 4 Snap the spacers in at the four mounting holes from the back in the intended slots Fig 3 5 Route the connection cable through the cut outs D in the back wall and hang the back on the screws 6 Tighten the screws Fig 4 Mount boards option 1 Snap the fastening supports included with the board into the intended holes A Fig 4 2 Fit circuit boards B Fig 4 Wiring The terminals ca...

Page 5: ...he base of the housing 4 Connect the mains to the mains supply terminals ground wire E null N and phase U 5 Secure the cable to the clips in the rear wall using cable ties Fig 6 A E bus from control unit B E Bus to other accessories E Bus Cable type IYSTY 2 x 2 x Ø 0 6 mm is recommended The total length of the E Bus cable must not exceed 500 m The power supply unit circuit board SMP14 and the opti...

Page 6: ...battery in the space provided in the base of the housing 2 Mount the battery holder angle 3 Connect the pre installed battery cables blue red Fig 9 Close and seal the housing 1 Glue the circuit diagram to the inside of the cover 2 Engage the cover in the retainer 3 Connect the earthing lead 1 Fig 9 to the cover 4 Lightly lift and close the cover 5 Screw the cover closed 6 Use eye 2 Fig 9 to seal W...

Page 7: ...duct indicates that the product is subject to EU Directive 2002 96 EC Proper disposal and separate collection of such equipment is intended to prevent potential harm to health and the environment They are prerequisites for re use and recycling of used electrical and electronic devices Detailed information on the disposal of used equipment can be obtained from your local authorities your waste disp...

Page 8: ...mbH Co oHG 76181 Karlsruhe Germany www buildingtechnologies siemens com 2009 Copyright by Siemens Building Technologies Liefermöglichkeiten und technische Änderungen vorbehalten Data and design subject to change without notice Document no A6V10236281 Edition 19 01 2009 ...

Reviews: