Siemens Building Technologies
Fire Safety & Security Products
01.2009
Risk of electrical shock
z
Ensure that the connection is secure and the circuit
breaker to the supply circuit is easily accessible when
operating the unit (e.g. fuse up to 16 A).
z
Do not connect any external consumers to the fuse.
z
Grounding has to adhere to the respective safety
regulations.
Device damage due to overvoltage
z
Connect the unit only to current sources with the
specified voltage. Information on the power supply is
available on the power supply unit / rating plate.
Risk of panic reactions
z
Prior to testing the system, make sure all important
persons involved and supporting authorities are
informed.
z
To avoid panic, all involved should be informed prior to
testing alarm facilities.
Danger of explosion
z
Make sure that the battery poles do not short circuit.
z
Please pay attention to battery polarity.
z
Always fasten the battery in place with the holder
intended for this purpose.
Technical data
Mains voltage
230 V AC, + 10 % / -15 %, 50 Hz
Power intake
max. 34 VA (at 230 V AC)
Mains supply fuse
160 mA T (Mains power)
Output voltage/current
13.7 V DC / 1.3 A
Max. ripple at 1.3 A
60 mV
Relay, single-pole
changeover
48 V / 5 A
Battery type according to
VdS
YUASA, Type NP7-12
(12 V / 7.2 Ah) recommended
Battery type not according
to VdS
YUASA, Type NP17-12
(12 V / 17 Ah) recommended
Operating temperature
0 to 40 °C
Steel housing
1.5 mm
Dimensions (W x H x D)
303 x 400 x 87.5 mm
Protection rating
IP30
Environmental class
II
Weight without battery
5.5 kg
Package contents
The SAP 14 package contains the following:
z
One SAP14 power supply unit
z
One battery holder
z
One set (4 units) of spacers
z
Installation instructions (de, en, fr, it)
z
Terminal connection diagram