background image

1

Fig. 1

1. Product description

The SAP 20 is a power supply unit suitable for an E-Bus and 
has an output voltage of 12 V at a maximum of 2.3 A.  The 
housing offers space for 7 type SMT 11 (transponder) or SMR 
11 (isolator/amplifi er) circuit boards and for a 12 V, 24 Ah 
battery.  At least one SMT 11 must be fi tted to use the cover 
tamper contact.

2. Supply package

The SAP 20 UK package contains the following:
- One SAP 20 power supply unit.
- One set (4 off) of spacers.
- One SLP 20 UK language kit complete with : 
  - Installation instructions.
  - One wiring diagram.

3. Mounting instructions

The SAP 20 external power supply unit is designed for moun-
ting in dry indoor rooms.  It must not be exposed to dripping 
or splashing water.

3.1 Open cover (Fig. 1)

1 - Slacken cover screw 

W

2 - Remove cover.

3.2 Product overview (Fig. 1)

- Housing 

E

.

- Power supply assembly circuit board SMP 20 

I

.

- Transformer SMU 31 

U

.

- Mains supply terminals 

with fuse.

- Eye

for sealing. 

- Tamper contact 

P

.

- Cable inlet 

Y

.

- Mounting holes for SMT 11 or SMR 11 circuit boards  
  (optional) 

Q

.

- Space for battery 

R

.

- Cover screws 

W

.

8AA10427 - F0 - 09/04/2003 - UK - 

SNR 557773.0-001

s

Installation instructions

External power supply unit

SAP 20

SLP 20 UK

20 800 225.0-010

Summary of Contents for SAP 20

Page 1: ...e with Installation instructions One wiring diagram 3 Mounting instructions The SAP 20 external power supply unit is designed for moun ting in dry indoor rooms It must not be exposed to dripping or splashing water 3 1 Open cover Fig 1 1 Slacken cover screw W 2 Remove cover 3 2 Product overview Fig 1 Housing E Power supply assembly circuit board SMP 20 I Transformer SMU 31 U Mains supply terminals ...

Page 2: ...ter U O must not be disturbed 3 3 Fit housing Fig 3 1 Mark the drilling position for the four mounting holes Q 2 Drill the holes and insert plugs 3 Screw in the screws leaving approximately 1 5 cm proud Fig 3B 4 From the back snap the spacers into the slots provided at the four mounting holes Fig 3A 5 Pass the connecting cable through the opening W provi ded and hang the housing base on the screws...

Page 3: ... the options SMT 11 SMR 11 must be connected to the central control unit via the E Bus B1 B2 B3 B4 It may be routed in parallel to other accessories If shielded cable is used the shield may not be laid on the housing of the SAP 20 The shields of all cables must be connected at one point e g at one of the NC terminals of SMT 11 or SAR 11 4 3 Tamper contact Fig 7 The tamper contact of the housing mu...

Page 4: ...he screws the cover can be lifted gently swung downwards and suspended in the base 7 Technical data Mains voltage 240V 50Hz Power consumption 230V 230mA Mains supply fuse 500 mA slow blowing Output power 12VDC 2 3 A Max ripple at 2 3 A 60mVpp Relay single pole changeover 48V 5A Battery min V 2 optional 12V 24Ah Operating temperature 10 C to 40 C Steel housing 1 5 mm Dimensions in mm H 500 x W 365 ...

Reviews: