NOTES:

1

.

Relay cont

act

s shown with power applied and system in normal

supervisory

, no 

alarm, condition.

2

.

See 

T

echnical Dat

a

 for comp

atible detectors.

3

.

Arrangement for photo detector and base located within air duct.

4

.

Use PE-1

1 with either DB-3S base and DB-ADPT

, or with

DB-1

1 base.

5

.

No more than two external detectors may be connected to

terminals 3 and 4 of 

TB1 of the SA-3I or SA-1

1P

.

6

.

Ensure that the incoming earth ground wire is properly connected

to the 

TB2 terminal marked 

GND

. If using an earth grounded

Figure 6

T

ypical Connections for Models SA-3I and SA-1

1P

CAUTION:

Do not use looped wire under terminal 5 of the DB-3S or DB-1

1 base.

Break wire run to provide supervision of both connections.

conduit, ensure that it is properly connected to the internal met

a

l

ground strap, using the proper conduit locking nut

s

Failure to

provide proper grounding may result in fat

al electrical shock.

7

.

Connect EOL device (1.3K, 1/2W resistor) to terminals 3 and 4 of

TB1 when no external detectors are connected.

8

.

When the relay cont

act

s are connected to a fire alarm system, the

trouble cont

act

s must be wired beyond the last detector so as not

to interfere with an alarm, as shown in Figure 7.

9

.

Use SA-3I or SA-1

1P

 relay for alarm signaling. Do not connect relay

modules directly to detectors.

Summary of Contents for SA-3I

Page 1: ... 2 above TECHNICAL DATA Smoke Detector Compatibility SA 3I Use Model DI B3 or DI B3H only SA 11P Use Model PE 11 AD 3I Satellite Use Model DI B3 or DI B3H only AD 11P Satellite Use Model PE 11 Operation Voltage and Current 120 VAC 50 60 Hz 32A max Alarm Relay DPDT contacts rated at 125 VAC 24 VDC 3A Resistive Trouble Relay SPDT contacts rated at 125 VAC 24 VDC 2A Resistive Smoke Detector Sensitivi...

Page 2: ...m from the filters and positioned so as to operate reliably in case of smoke in any part of the air stream In instances where the filters are capable of removing smoke a detector should be installed both upstream and down stream from the filters The air duct detectors because they use sampling tubes which monitor the full width of an air duct overcome the limitations of spot type smoke and heat de...

Page 3: ... 16 17 COMPONENT COMPONENT COMPONENT COMPONENT 2 Sampling Tube Gasket 1 Housing 1 Inlet Sampling Tube 1 Outlet Sampling Tube 1 Template 2 Screw No 10 1 2 Lockwasher 1 Rubber Stopper 3 Bracket 3 Screw 3 16 1 Plug 1 Detector PE 11 1 Ionization Detector Cover 1 Detector DI B3 DI B3H 1 Sensitivity Test Jack Lid 1 Cover Gasket 1 PE 11 Detector Cover 1 DB ADPT Base Adapter 12 18 3 Screw 8 32 8 Screw No ...

Page 4: ...ockwashers 8 e Cut a 12 inch by 12 inch access hole in the duct adjacent to the housing to permit checking and cleaning of the sampling tubes The access hole must be covered and sealed when not in use Sampling Tube Selection To insure accurate air sampling inlet sampling tubes are available in four lengths To select the appropriate length determine the outside width of the duct Select the sampling...

Page 5: ...uld be taken by qualified personnel in accordance with the PDM 3 Instructions P N 315 085535 ELECTRICAL WIRING The Air Duct Detector Model SA 3I 11P is interconnected and wired following the wiring diagram in Figure 6 Each model requires a two wire circuit of 18 AWG min thermoplastic fixture wire enclosed in conduit or of 18 AWG min limited energy shielded cable without conduit if permitted by loc...

Page 6: ... for Models SA 3I and SA 11P CAUTION Do not use looped wire under terminal 5 of the DB 3S or DB 11 base Break wire run to provide supervision of both connections conduit ensure that it is properly connected to the internal metal ground strap using the proper conduit locking nuts Failure to provide proper grounding may result in fatal electrical shock 7 Connect EOL device 1 3K 1 2W resistor to term...

Page 7: ...to place Installation Removal of PE 11 Detector in Base Adapter To Install Align detector with base and insert detector Rotate detector counterclockwise while gently pressing on it until the detector drops fully into base Then rotate the detector clockwise until it stops and locks in place Insert optional locking screw Order Model LK 11 To Remove Rotate the detector counterclockwise until stop is ...

Page 8: ... listed limits MAINTENANCE The performance of the air duct detector unit may be adversely affected by dirt or foreign matter on the sampling tubes or detector If the air holes in the inlet sampling tube become restricted the unit cannot receive a proper air sample and performance is impaired It is recommended that the sampling tubes be checked and cleaned periodically The detector maintenance prog...

Reviews: