6
NOTES:
1
.
Relay cont
act
s shown with power applied and system in normal
supervisory
, no
alarm, condition.
2
.
See
T
echnical Dat
a
for comp
atible detectors.
3
.
Arrangement for photo detector and base located within air duct.
4
.
Use PE-1
1 with either DB-3S base and DB-ADPT
, or with
DB-1
1 base.
5
.
No more than two external detectors may be connected to
terminals 3 and 4 of
TB1 of the SA-3I or SA-1
1P
.
6
.
Ensure that the incoming earth ground wire is properly connected
to the
TB2 terminal marked
GND
. If using an earth grounded
Figure 6
T
ypical Connections for Models SA-3I and SA-1
1P
CAUTION:
Do not use looped wire under terminal 5 of the DB-3S or DB-1
1 base.
Break wire run to provide supervision of both connections.
conduit, ensure that it is properly connected to the internal met
a
l
ground strap, using the proper conduit locking nut
s
.
Failure to
provide proper grounding may result in fat
al electrical shock.
7
.
Connect EOL device (1.3K, 1/2W resistor) to terminals 3 and 4 of
TB1 when no external detectors are connected.
8
.
When the relay cont
act
s are connected to a fire alarm system, the
trouble cont
act
s must be wired beyond the last detector so as not
to interfere with an alarm, as shown in Figure 7.
9
.
Use SA-3I or SA-1
1P
relay for alarm signaling. Do not connect relay
modules directly to detectors.