background image

5

Installation of the Sampling Tubes
a.

Before installing the tubes, cut a 7/8-inch hole in the duct wall that is directly opposite the inlet
sampling chamber hole in the detector housing.  This will allow the inlet tube to protrude through
the duct.

b.

Attach brackets (10) to the inlet and outlet air sampling tubes with 3/16 screws (11). 
NOTE:  When attaching brackets, be sure to align tubes properly (See Figure 4).

c.

Install the inlet tube by inserting it in through the air sampling chamber as shown in Figure 3 (3).
Face sampling tube holes into the air stream (Figure 4), and secure to the housing with 8/32
screws (12).

d.

Install the outlet tube (4) by inserting it into the upper socket of the air sampling chamber with the
scarfed end facing downstream (See Figure 4).  Secure the bracket to the housing with an 8/32
screw.

e.

Make sure no sampling holes extend beyond the ductway, that the stopper remains firmly in
position, and that the duct hole is sealed around the protruding sampling tube.

Air Duct Sampling Tube Pressure Measurement

The

 

Model PDM-3 Pressure Differential Measuring device should be used to ensure that the

sampling tube pressure differential is within the specified limits (See TECHNICAL DATA).  Mea-
surements should be taken by qualified personnel in accordance with the PDM-3 Instructions,
P/N 315-085535.

ELECTRICAL WIRING
The Air Duct Detector Model SA-3I/-11P is interconnected and wired following the wiring diagram in
Figure 6. Each model requires a two-wire circuit of 18 AWG min thermoplastic fixture wire, enclosed
in conduit, or of 18 AWG min limited energy shielded cable, without conduit, if permitted by local
building codes.

Control of Normally Energized and De-Energized Devices

The Model SA-3I/-11P can be wired for direct relay control of normally energized and deenergized
devices as follows (Refer to Figure 5).

a. Wire normally energized devices (fans, blowers, etc.) to the NC contacts between terminals

10 and 11 or 13 and 14 in order to shut down these devices on alarm.

b. Wire normally de-energized devices (extinguishing smoke removal fan, etc.) to the

NO contacts between terminals 9 and 10 or 12 and 13 in order to activate these
devices on alarm.

NOTE:
1.

All relay contacts are shown with system in the normal supervisory, no alarm, condition.

WARNING:

If the alarm relay contacts on the control board are being used to control 120 VAC operated equip-
ment, then ensure that earth ground is properly connected to the internal ground strap, using the
proper conduit lock nuts. Failure to provide proper grounding may result in fatal electrical shock.

Figure 5

Connections for Control of Normally Energized

and De-Energized Devices

Summary of Contents for SA-3I

Page 1: ... 2 above TECHNICAL DATA Smoke Detector Compatibility SA 3I Use Model DI B3 or DI B3H only SA 11P Use Model PE 11 AD 3I Satellite Use Model DI B3 or DI B3H only AD 11P Satellite Use Model PE 11 Operation Voltage and Current 120 VAC 50 60 Hz 32A max Alarm Relay DPDT contacts rated at 125 VAC 24 VDC 3A Resistive Trouble Relay SPDT contacts rated at 125 VAC 24 VDC 2A Resistive Smoke Detector Sensitivi...

Page 2: ...m from the filters and positioned so as to operate reliably in case of smoke in any part of the air stream In instances where the filters are capable of removing smoke a detector should be installed both upstream and down stream from the filters The air duct detectors because they use sampling tubes which monitor the full width of an air duct overcome the limitations of spot type smoke and heat de...

Page 3: ... 16 17 COMPONENT COMPONENT COMPONENT COMPONENT 2 Sampling Tube Gasket 1 Housing 1 Inlet Sampling Tube 1 Outlet Sampling Tube 1 Template 2 Screw No 10 1 2 Lockwasher 1 Rubber Stopper 3 Bracket 3 Screw 3 16 1 Plug 1 Detector PE 11 1 Ionization Detector Cover 1 Detector DI B3 DI B3H 1 Sensitivity Test Jack Lid 1 Cover Gasket 1 PE 11 Detector Cover 1 DB ADPT Base Adapter 12 18 3 Screw 8 32 8 Screw No ...

Page 4: ...ockwashers 8 e Cut a 12 inch by 12 inch access hole in the duct adjacent to the housing to permit checking and cleaning of the sampling tubes The access hole must be covered and sealed when not in use Sampling Tube Selection To insure accurate air sampling inlet sampling tubes are available in four lengths To select the appropriate length determine the outside width of the duct Select the sampling...

Page 5: ...uld be taken by qualified personnel in accordance with the PDM 3 Instructions P N 315 085535 ELECTRICAL WIRING The Air Duct Detector Model SA 3I 11P is interconnected and wired following the wiring diagram in Figure 6 Each model requires a two wire circuit of 18 AWG min thermoplastic fixture wire enclosed in conduit or of 18 AWG min limited energy shielded cable without conduit if permitted by loc...

Page 6: ... for Models SA 3I and SA 11P CAUTION Do not use looped wire under terminal 5 of the DB 3S or DB 11 base Break wire run to provide supervision of both connections conduit ensure that it is properly connected to the internal metal ground strap using the proper conduit locking nuts Failure to provide proper grounding may result in fatal electrical shock 7 Connect EOL device 1 3K 1 2W resistor to term...

Page 7: ...to place Installation Removal of PE 11 Detector in Base Adapter To Install Align detector with base and insert detector Rotate detector counterclockwise while gently pressing on it until the detector drops fully into base Then rotate the detector clockwise until it stops and locks in place Insert optional locking screw Order Model LK 11 To Remove Rotate the detector counterclockwise until stop is ...

Page 8: ... listed limits MAINTENANCE The performance of the air duct detector unit may be adversely affected by dirt or foreign matter on the sampling tubes or detector If the air holes in the inlet sampling tube become restricted the unit cannot receive a proper air sample and performance is impaired It is recommended that the sampling tubes be checked and cleaned periodically The detector maintenance prog...

Reviews: