HVAC Products
CC1B7865en
05.12.2002
49/57
9. Self-setting function
Start
t
w
x
7865d13/1099
The controlled system data recorded for the forced oscillations are used to calculate the
controller parameters «rt, dt, Pb.1» and a filter time constant for actual value filtering
that is optimized for this controlled system.
-
High-fire operation in the «modulating burner» mode
-
The thermostat function (relay 1) must be constantly activated, otherwise «
tunE»
will
be canceled and no optimized controller parameters will be adapted
-
The above mentioned actual value oscillations during self-setting may not exceed the
upper threshold of the thermostat function (increase if necessary, and lower the
setpoint)
Conditions