8/12
Siemens
Heating Controller RVP201, RVP211
CE1N2464en
Building Technologies
2017-07-31
Technical Data
Rated operating voltage
AC 230 V ( 10 %)
Frequency
50 Hz
Power consumption (no external load)
7 VA
External supply line protection
Slow-blow fuse max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to
EN 60898
Switching capacity
AC 24…230 V, AC 0.02…2 (2) A
Rated current of ignition transformer
max.1 A ( max. 30 s)
Switch-on current of ignition transformer
max.10 A (max. 10 ms)
External supply line protection
See section power supply
Copper cable 0.6 mm
30 m
Copper cable 0.5 mm
2
50 m
Copper cable 1.0 mm
2
80 m
Copper cable 1.5 mm
2
120 m
Screw terminals for wire section
up to 2.5 mm
2
Setpoint of normal room temperature
20 ± 0…8 °C
Setback for reduced room temperature –12…0 K
Setpoint of d.h.w. temperature (only
with the RVP211)
10…60 °C
Slope of heating curve
0.25…4
Max. limit of flow or boiler temperature 10…100 °C
ECO heating limit
–10…+8 K (referred to normal setpoint)
Authority of room temperature
0…100 %
Switching differential with two-position
control
1…20 K
Analog time switches
12 hours
Digital weekly time switch
with backup battery
Standards, directives and
approvals
Product standard
EN 60730-1
Automatic electrical controls for household and
similar use
Electromagnetic compatibility
(Applications)
For use in residential, commerce, light-
industrial and industrial environments
EU conformity (CE)
CE1T2464en_C1 *)
EAC conformity
Eurasia conformity
Environmental compatibility Product environmental declaration
(contains data on RoHS compliance,
materials composition, packaging,
environmental benefit, disposal)
CE1E2464 *)
Eco design and labeling di-
rectives
Class Efficiency gain
Application with one room temperature sensor and one out-
door temperature sensor and on/off control
VII
3.5%
Application with one room temperature sensor and on/off
control
III
1.5%
*) The documents can be downloaded from
http://siemens.com/bt/download
.
Power supply
Output relays
Permissible cable
lengths to the sensors
and the room unit
Connection terminals
Setting ranges
Backup of time
switches