6/12

Siemens

Heating Controller RVP201, RVP211

CE1N2464en

Building Technologies

2017-07-31

  Changeover of operating mode and room setpoint as well as room temperature read-

justment with the QAA50.. room unit

  Overriding of setpoints and heating program with the QAW70 room unit
  Changing the operating mode with an external switching contact (refer to "Mechani-

cal design")

Mechanical design

The RVP201/211 is comprised of controller insert, which houses the electronics, the
power section, the output relays and all operating elements, and the base, which car-
ries the connection terminals. The operating elements for the end-user are located
behind a transparent cover.
The operating elements for the heating engineer can be accessed after removal of the
time switch or when the cover is opened.

2

46

4Z

04

1

2

3

4

5

6

7

8

9 10

11 12

Setting elements (view without time switch)

1

Opening for the time switch

2

LED for "Override"

3

Operating mode selector

4

Setting knob the for heating curve

5

Setting knob the for setback

6

Setting knob for the d.h.w. temperature (only with the RVP211)

7

Setting knob for the normal room temperature

8

Coding switches

9

Setting potentiometer for the authority of room temperature and quick setback active / inactive

10 

Setting potentiometer for the max. limitation of flow or boiler temperature

11  Setting potentiometer for the ECO heating limit
12  Setting potentiometer for the switching differential

The controller insert is secured to the base by means of two screws. The cover can be
sealed.
The RVP201/211 can be fitted in three different ways:

  Wall mounting (on a wall, in a control panel, etc.)
  Rail mounting (on a standard top hat rail)
  Flush panel mounting (control panel door, etc)

When connecting an external switching contact to the controller's terminals A6-MD, the
operating mode can be selected from a remote location:

  Contact closed: controller is in protection mode
  Contact open: controller uses the operating mode selected with the slider

Remote operation

Controller

Switching contact

Summary of Contents for RVP201.0

Page 1: ...e end user Operating voltage AC 230 V Use Types of houses and buildings Small multi family houses Single family houses or holiday houses Smaller non residential buildings Types of plant Heating zones with their own heat generating equipment and own d h w heating Types of heating systems Radiator convector underfloor and ceiling heating systems as well as radiant panels Functions The RVP201 211 hea...

Page 2: ... d h w heating Setback mode Continuous heating to the reduced temperature with ECO automatic energy saver d h w heating Normal mode Continuous heating to the normal temperature no ECO automatic energy saver d h w heating Protection mode Frost protection is ensured Manual operation Control switched off d h w charging pump and heating circuit pump running Automatic d h w heating Heating control in p...

Page 3: ...0 or RVP211 0 plus the required time switch AUZ3 7 or AUZ3 1 must be ordered Sensors room unit actuator and valve must be ordered as separate items Product documentation Type of documentation Document no Part no Basic Documentation P2464 Installation Instructions languages de en fr nl sv fi da it es el G2464 74 319 0614 0 Operating Instructions languages de en fr nl sv fi da it es el B2464 74 319 ...

Page 4: ...the boiler temperature falls below 5 C the burner will be switched on to maintain a minimum boiler temperature When there is no demand for heat and during quick setback the boiler will be switched off In the case of flow temperature control with a mixing valve d h w heating is ensured with a charging pump With boiler temperature control the d h w is heated either with a charging pump or changeover...

Page 5: ...K When the room temperature reaches a level which lies 0 25 K below the setpoint of the normal temperature boost heating will be switched off Boost heating necessitates a room unit When changing from the normal temperature to the reduced temperature or protection mode the heating will be shut down until the respective room temperature setpoint is reached Quick setback necessitates a room unit This...

Page 6: ...r Override 3 Operating mode selector 4 Setting knob the for heating curve 5 Setting knob the for setback 6 Setting knob for the d h w temperature only with the RVP211 7 Setting knob for the normal room temperature 8 Coding switches 9 Setting potentiometer for the authority of room temperature and quick setback active inactive 10 Setting potentiometer for the max limitation of flow or boiler temper...

Page 7: ... be made by the heating engineer Slope of heating curve Authority of room temperature ECO heating limit Maximum limitation of the flow or boiler temperature Type of regulating unit mixing valve or burner Type of control three or two position Frost protection activated or deactivated Priority of d h w heating only with the RVP211 The controller is supplied complete with installation instructions an...

Page 8: ...limit 10 8 K referred to normal setpoint Authority of room temperature 0 100 Switching differential with two position control 1 20 K Analog time switches 12 hours Digital weekly time switch with backup battery Standards directives and approvals Product standard EN 60730 1 Automatic electrical controls for household and similar use Electromagnetic compatibility Applications For use in residential c...

Page 9: ... Controller insert Light grey RAL 7035 Terminal base Pigeon blue RAL 5014 Operation EN 60721 3 3 Transport EN 60721 3 2 Storage EN 60721 3 1 Climatic conditions class 3K5 class 2K3 class 1K3 Temperature 0 50 C 25 70 C 20 65 C Humidity 95 r h non condensing 95 r h 95 r h non condensing Mechanical conditions class 3M2 class 2M2 class 1M2 Use above sea level max 3000 m above sea level Protective data...

Page 10: ... heating circuit pump and d h w charging pump d h w charging pump only with the RVP211 Connection of burner boiler temperature control Connection of two position actuator flow temperature control Connection of actuator for changeover valve only with the RVP211 A6 Room unit M1 Heating circuit pump B1 Flow or boiler temperature sensor M3 D h w charging pump only with the RVP211 B3 D h w temperature ...

Page 11: ...on the burner d h w heating with changeover valve B9 A6 2462S05 B3 E3 M3 Flow temperature control three or two position control acting on the seat or slipper valve d h w heating with charging pump A6 Room unit E3 D h w storage tank B1 Boiler or flow temperature sensor M1 Heating circuit pump B3 D h w temperature sensor M3 D h w charging pump B9 Outside sensor N1 Controller RVP201 211 E1 Boiler Y1 ...

Page 12: ...3 EN 60715 max 5 M16 EN 50262 22 max 8 Dimensions in mm For more detailed information about the RVP201 211 refer to the Basic Documentation P2464 Published by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2007 Delivery and technical specification...

Reviews: