Building Technologies
74 319 0619 0 a
17.04.2008
61/288
en
Space heating mode D.h.w.
0 =
PROTEC-
TION
OFF
1 =
AUTO OFF
2 =
REDUCED OFF
3 =
NORMAL OFF
4 =
PROTEC-
TION
ON
5 =
AUTO ON
6 =
REDUCED ON
7 =
NORMAL ON
8 =
AUTO ON,
24 h / day
172 Operating mode
when terminals H1–
M are linked
0
(0…9)
.........................
9 =
NORMAL ON,
24 h / day
173 Amplification of
locking signal
100 %
(0…200)
....................
%
Response to locking signals
174 Pump overrun time
6 min
(0…40)
................
min
175 Periodic pump run
(pump kick)
0
(0 / 1)
.........................
0 = no periodic pump run
1 = weekly pump run enabled
176 Winter- / summer-
time changeover
25.03
(01.01 … 31.12)
.........................
Setting: Earliest possible
changeover date
177 Summer- / winter-
time changeover
25.10
(01.01 … 31.12)
.........................
Setting: Earliest possible
changeover date
178 Clock operation
0
(0…3)
.........................
0 = autonomous clock in the
controller
1 = clock from bus (slave), with
no remote setting
2 = clock from bus (slave), with
remote setting
3 = controller is the central
clock (master)
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - [email protected] 0844 556 1818