Block “Switching program 3”
151 Weekday (for
switching program
3)
1-7
(1…7)
.........................
1 = Monday
2 = Tuesday, etc.
1-7 = entire week
152 Start of first ON
period
06:00
(00:00…24:00)
.........................
153 End of first ON
period
22:00
(00:00…24:00)
.........................
154 Start of second ON
period
--:--
(00:00…24:00)
.........................
155 End of second ON
period
--:--
(00:00…24:00)
.........................
156 Start of third ON
period
--:--
(00:00…24:00)
.........................
157 End of third ON
period
--:--
(00:00…24:00)
.........................
Switching program 3
--:-- = period inactive
Block “Service functions and general settings”
161 Outside tempera-
ture simulation
--.- °C
(--.- /
−
50…+50)
...................
°C
Simulation automatically termi-
nated after 30 minutes
--.- = no simulation
162 Relay test
0
(0…13)
0 = normal operation
1 = all contacts open
2 = burner stage 1 ON K4
3 = burner stages 1 ON K4
and 2 ON / burner modula-
tion actuator OPEN K5
4 = circulating pump / bypass
pump ON M1
5 = charging pump ON M3
6 = heating circuit mixing valve
OPEN Y1
7 = heating circuit mixing valve
CLOSED Y2