Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity Levels
Dry Heat
Test Bd
85 °C (185
°F), 16 Hours
IEC 60068-2-2
Dry Heat Storage
Test Bd
85 °C (185
°F), 16 Hours
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Dd
95% (Non-
Condensing),
55 °C (131
°F), 6 Cycles
IEC 60068-2-14
Change of
Temperature
Test Nb
5 Cycles @
-40 to 85 °C
(-40 to 185 °F)
IEC 60068-2-78
Humidity (Damp
Heat, Cyclic)
Test Cab
10 Days @ 55 °C
(131 °F), 6 Cycles
IEC 60255-21-1
Vibration
2 g @ 10 to 150 Hz
Class 2
IEC 60255-21-2
Shock
30 g @ 11 ms
Class 2
IEC 60255-21-2
Bump
10 g @ 16 ms
Class 1
IEC 60255-21-3
Seismic
Method A
Class 2
IEC 60529
Ingress Protection
IP4x
RUGGEDCOM RSG910C
Installation Manual, 04/2022, C79000-G8976-1405-11
39