Siemens REV17 Series Instructions Manual Download Page 9

9 / 13 

Siemens 

Room temperature controller REV17.. 

CE1N2203en 

Building Technologies   

24.04.2008 

Access to the expert level 

Set the program selection slider to RUN. Press 

 and 

 simultaneously for 3 seconds, release the buttons, and 

within 3 seconds press and hold down 

 and 

 simultaneously for 3 seconds, release 

, and press 

 for another 

3  seconds. This releases the engineering settings. 

 is displayed.

 

The display first shows language selection with Code 00. Press the buttons 

 or 

 to navigate the settings. 

Confirm settings by pressing 

.

 

Press the operating mode selector 

 to exit the engineering settings. 

Code list 

 
This entry has no effect if the radio clock either is inactive or not available. 
The time signal received from Frankfurt is shifted by the value set in Code 30 (time zone) 
if the radio clock is active.

 

The time is always changed over at 2 a.m. on the Sunday preceding the set date if there 
is no radio clock or if it is inactive. The time change is shifted by the value set in Code 30 
(time zone) when the radio clock is active.

 

The time is always changed over at 3 a.m. on the Sunday preceding the set date if there 
is no radio clock or if it is inactive. 

Functional check 

a) 

Check the display. If there is no display, check insertion and function of the batteries.

 

b)  Operating mode “Continuous comfort mode“ 

, read displayed temperature. 

c) 

Set the temperature setpoint higher than the displayed room temperature (see operating 
instructions).

 

d) 

The relay and, as a result, the actuating device must switch at the latest after one minute. 
Symbol 

 is displayed. If not displayed:

 

  Check actuating device and wiring. 

  It is possible that in heating mode the room temperature is higher than the set 

temperature setpoint. 

e)  Set the temperature setpoint for operating mode “Continuous comfort mode“ 

 to the 

desired value. 

f)  Select the desired operating mode. 

Function block

 

Code

 

Name

 

Factory setting

 

Your setting

 

00 

Language

 

English

 

 

01 

Sensor calibration

 

off  

Basic settings

 

02 

Switching differential 2-point

 

0.5 °C 

 

10 

Illumination time 

 

10 seconds 

 

11 

Background brightness

 

0  

LCD  
optimization

 

12 

Contrast

 

0  

30 

Time zone 
Deviation from time signal in Frankfurt 
(Central European Time CET) (see Note 1)

 

0 hours

 

 

31 

Start of daylight saving time (see Note 2)

 

31. March 31 (03-31)

 

 

Clock settings

 

32 

End of daylight saving time (see Note 3)

 

31. October 31 (10-
31)

 

 

Note 1: 

Note 2: 

Note 3: 

Summary of Contents for REV17 Series

Page 1: ...ption day 24 hour operation with max 3 heating phases A separate temperature setpoint can be entered in automatic mode and for the exception day for each heating phase To control a heating zone Use Room temperature control in Single family and vacation homes Apartments and offices Individual rooms and professional office facilities Commercially used spaces Control for the following equipment Magne...

Page 2: ...ler with 7 day weekday weekend time switch REV17 Room temperature controller with 7 day weekday weekend time switch and receiver for time signal from Frankfurt Germany DCF77 REV17DC Ordering Please indicate the type number as per the Type summary when ordering Delivery The controller is supplied with batteries Mechanical design Plastic casing with an easy to read display and large numbers easily a...

Page 3: ...tive Without language selection C F Temperature unit C or F Heating pump on Time signal from Frankfurt Remote control active 2 Operating mode selector Automatic weekly mode with max three heating phases per day Exception day with max three heating phases Continuous comfort mode continuous comfort temperature Continuous energy saving mode continuous energy saving temperature Frost protection mode c...

Page 4: ... selectable temperature for a freely selectable period of time In party mode symbol is displayed along with the end of party mode 6 Minus button Decrease values set time or make a selection 7 Program selection slider Time Day Month Year 2 spaces for day month and year Block of weekdays or block of weekend 1 2 or 3 heating phases Start Heating phase 1 Start Heating phase 2 Start Heating phase 3 Set...

Page 5: ...t the setpoints for the weekly and 24 hour operating modes Setting range for all setpoints without setpoint limitation 3 35 C Setting range for all setpoints with setpoint limitation 16 35 C Factory settings Heating 20 C 16 C 8 C 12 C Factory settings Switching times Heating phases P1 P2 P3 P4 P5 P6 1 07 00 23 00 PASS PASS PASS PASS 2 06 00 08 00 17 00 22 00 PASS PASS 3 06 00 08 00 11 00 13 00 17 ...

Page 6: ...ate the Remote control temperature setpoint in the controller Changeover takes place by making a potential free contact connected to terminals T1 and T2 A flashing symbol indicates active remote control mode After the contact opens the previously set operating mode is reactivated Operation according to controller setting Temperature setpoint remote control active T2 T1 2252Z05 T2 T1 2252Z06 Suitab...

Page 7: ...played room temperature does not match the measured room temperature the temperature sensor can be recalibrated Set DIP switch to ON and press the DIP switch reset button CAL symbol is displayed The currently measured temperature flashes Press or to recalibrate by max 5 C Set DIP switch to OFF and press the DIP switch reset button to save the settings The minimum setpoint limitation of 16 C preven...

Page 8: ...h OFF Time signal DCF77 from Frankfurt Germany Press the DIP switch reset button to save the settings During startup REV DC synchronizes automatically to the time signal DCF77 from Frankfurt Germany Synchronization takes max 10 minutes Synchronization restarts each time you press the button or move the program selection slider from the RUN position during these 10 minutes Siemens recommends to set...

Page 9: ... the Sunday preceding the set date if there is no radio clock or if it is inactive Functional check a Check the display If there is no display check insertion and function of the batteries b Operating mode Continuous comfort mode read displayed temperature c Set the temperature setpoint higher than the displayed room temperature see operating instructions d The relay and as a result the actuating ...

Page 10: ...efrigeration sources Mounting height is approx 1 5 m above the floor You can mount the unit on most commercially available recessed conduit boxes or directly on the wall Begin installation by first attaching and wiring the base You can mount the base on most commercially available recessed conduit boxes or directly on the wall Then insert the controller from top to bottom into the base For more in...

Page 11: ...al value measurement Actual value display Time display 0 2 C 10 min 0 1 C 0 2 C 1 min CE conformity Electromagnetic compatibility Low voltage directive 2004 108 EEC 2006 95 EC C tick N474 Automatic electrical controls for household and similar use EN 60 730 1 Electromagnetic compatibility Immunity Emissions EN 61000 6 2 EN 61000 6 3 Operation Climatic conditions Temperature Humidity 3K3 as per IEC...

Page 12: ...ignal M1 Circulating pump Y1 Actuating device N1 REV17 controller Application examples T T F1 F2 N1 M1 Y2 2252S01 T T F1 F2 N1 M1 Y2 2252S02 T T Instantaneous water heater Atmospheric gas burner N1 Y4 2252S03 N1 Y3 T T T N1 Y1 2252S04 M1 Zone valve Circulating pump with precontrol by manual mixing valve F1 Thermal reset limit thermostat Y1 3 port valve with manual adjustment F2 Manual reset safety...

Page 13: ...13 13 Siemens Room temperature controller REV17 CE1N2203en Building Technologies 24 04 2008 Dimensions 130 94 134 5 82 56 16 2 83 5 13 56 Ø 6 0 30 2206M03 2008 Siemens Switzerland Ltd Subject to change ...

Reviews: