The REV17… is a two-position controller with PID control. The room temperature is 
controlled through cyclic switching of an actuating unit.

 

DIP switches 4 ON and 5 ON: 

PID self-learning

 

 

Adaptive control for all applications. 

DIP switches 4 ON and 5 OFF:   

PID 6

 

 

Fast controlled system for applications in locations with  

 

large temperature deviations. 

DIP switches 4 OFF and 5 ON:   

PID 12

 

 

Normal controlled system for applications in locations with 

  

normal temperature deviations. 

DIP switches 4 OFF and 5 OFF: 

2-point

 

 

For complex controlled systems, simple two-position controller with   

 

0.5 °C switching difference   (factory setting).

 

Press the DIP switch reset button to save the settings. 
 
 
Only applicable with controlled circulating pump or valve! 
This function protects the pump or valve during extended OFF periods against possible 
seizure caused by liming. Periodic pump run is activated every 24 hours at 12 p.m. for 
three minutes (symbol 

 is displayed during active pump run).

 

DIP switch ON:  Pump run On.

 

DIP switch OFF: Pump run On (factory setting).

 

Press the DIP switch reset button to save the settings. 
 
 
Only applicable to REV..DC (with integrated DCF77 receiver to receive time signal from 
Frankfurt, Germany)! 
DIP switch ON:  Clock run by controller-internal quartz.

 

DIP switch OFF: 

 Time signal DCF77 from Frankfurt, Germany.

 

Press the DIP switch reset button to save the settings. 
 
 
During startup, REV..DC synchronizes automatically to the time signal (DCF77) from 
Frankfurt, Germany. Synchronization takes max. 10 minutes. Synchronization restarts 
each time you press the button or move the program selection slider from the RUN 
position during these 10 minutes. Siemens recommends to set the desired settings upon 
startup, install the REV..DC in the desired location, and not carry out any actions on the 
REV..DC for the next 10 minutes.

 

In normal operation, the REV..DC synchronizes to the radio clock every day at 3:10 a.m. 
The time signal from Frankfurt is modulated to a radio signal. The reception of this radio 
signal depends on the distance to Frankfurt, atmospheric conditions as well as the 
location where the REV..DC is installed. Siemens cannot guarantee that the REV..DC 
can receive the time signal from Frankfurt at any time and any place.

 

The radio clock symbol is deactivated and an error message is displayed if the clock was not 
able to synchronize the time for 7 consecutive days. The controller then runs on the internal 
quartz.

 

 
 
After you change one or several DIP switch positions, you must press the DIP switch 
reset button to reset the DIP switch. 
Otherwise, the previous setting remains active! 

D

 Control behavior:  

    DIP switches 4 and 5 

E

 Periodic pump run 

    and anti-lime function:  
    DIP switch 6 

F

 Radio clock:  

    DIP switch 10 

   Note 
   on synchronization 

    Note 
   on reception 

    No reception 

G

 DIP switch reset 

 

    

ON

1

3

4

2

22

11Z

32

5

6

7

8

9

 

Summary of Contents for REV17 Series

Page 1: ...ption day 24 hour operation with max 3 heating phases A separate temperature setpoint can be entered in automatic mode and for the exception day for each heating phase To control a heating zone Use Room temperature control in Single family and vacation homes Apartments and offices Individual rooms and professional office facilities Commercially used spaces Control for the following equipment Magne...

Page 2: ...ler with 7 day weekday weekend time switch REV17 Room temperature controller with 7 day weekday weekend time switch and receiver for time signal from Frankfurt Germany DCF77 REV17DC Ordering Please indicate the type number as per the Type summary when ordering Delivery The controller is supplied with batteries Mechanical design Plastic casing with an easy to read display and large numbers easily a...

Page 3: ...tive Without language selection C F Temperature unit C or F Heating pump on Time signal from Frankfurt Remote control active 2 Operating mode selector Automatic weekly mode with max three heating phases per day Exception day with max three heating phases Continuous comfort mode continuous comfort temperature Continuous energy saving mode continuous energy saving temperature Frost protection mode c...

Page 4: ... selectable temperature for a freely selectable period of time In party mode symbol is displayed along with the end of party mode 6 Minus button Decrease values set time or make a selection 7 Program selection slider Time Day Month Year 2 spaces for day month and year Block of weekdays or block of weekend 1 2 or 3 heating phases Start Heating phase 1 Start Heating phase 2 Start Heating phase 3 Set...

Page 5: ...t the setpoints for the weekly and 24 hour operating modes Setting range for all setpoints without setpoint limitation 3 35 C Setting range for all setpoints with setpoint limitation 16 35 C Factory settings Heating 20 C 16 C 8 C 12 C Factory settings Switching times Heating phases P1 P2 P3 P4 P5 P6 1 07 00 23 00 PASS PASS PASS PASS 2 06 00 08 00 17 00 22 00 PASS PASS 3 06 00 08 00 11 00 13 00 17 ...

Page 6: ...ate the Remote control temperature setpoint in the controller Changeover takes place by making a potential free contact connected to terminals T1 and T2 A flashing symbol indicates active remote control mode After the contact opens the previously set operating mode is reactivated Operation according to controller setting Temperature setpoint remote control active T2 T1 2252Z05 T2 T1 2252Z06 Suitab...

Page 7: ...played room temperature does not match the measured room temperature the temperature sensor can be recalibrated Set DIP switch to ON and press the DIP switch reset button CAL symbol is displayed The currently measured temperature flashes Press or to recalibrate by max 5 C Set DIP switch to OFF and press the DIP switch reset button to save the settings The minimum setpoint limitation of 16 C preven...

Page 8: ...h OFF Time signal DCF77 from Frankfurt Germany Press the DIP switch reset button to save the settings During startup REV DC synchronizes automatically to the time signal DCF77 from Frankfurt Germany Synchronization takes max 10 minutes Synchronization restarts each time you press the button or move the program selection slider from the RUN position during these 10 minutes Siemens recommends to set...

Page 9: ... the Sunday preceding the set date if there is no radio clock or if it is inactive Functional check a Check the display If there is no display check insertion and function of the batteries b Operating mode Continuous comfort mode read displayed temperature c Set the temperature setpoint higher than the displayed room temperature see operating instructions d The relay and as a result the actuating ...

Page 10: ...efrigeration sources Mounting height is approx 1 5 m above the floor You can mount the unit on most commercially available recessed conduit boxes or directly on the wall Begin installation by first attaching and wiring the base You can mount the base on most commercially available recessed conduit boxes or directly on the wall Then insert the controller from top to bottom into the base For more in...

Page 11: ...al value measurement Actual value display Time display 0 2 C 10 min 0 1 C 0 2 C 1 min CE conformity Electromagnetic compatibility Low voltage directive 2004 108 EEC 2006 95 EC C tick N474 Automatic electrical controls for household and similar use EN 60 730 1 Electromagnetic compatibility Immunity Emissions EN 61000 6 2 EN 61000 6 3 Operation Climatic conditions Temperature Humidity 3K3 as per IEC...

Page 12: ...ignal M1 Circulating pump Y1 Actuating device N1 REV17 controller Application examples T T F1 F2 N1 M1 Y2 2252S01 T T F1 F2 N1 M1 Y2 2252S02 T T Instantaneous water heater Atmospheric gas burner N1 Y4 2252S03 N1 Y3 T T T N1 Y1 2252S04 M1 Zone valve Circulating pump with precontrol by manual mixing valve F1 Thermal reset limit thermostat Y1 3 port valve with manual adjustment F2 Manual reset safety...

Page 13: ...13 13 Siemens Room temperature controller REV17 CE1N2203en Building Technologies 24 04 2008 Dimensions 130 94 134 5 82 56 16 2 83 5 13 56 Ø 6 0 30 2206M03 2008 Siemens Switzerland Ltd Subject to change ...

Reviews: