The switching program can be used as a 7-day or 24-hour program, depending on
programming. It is also possible to select one of the continuous operating modes
with which the switching program is not used.
With the 7-day program, all individual days, working days (1-5), weekend (6-7), or the
entire week (1-7) can be programmed.
For each heating / cooling period, 3 different switching patterns are available.
There is a choice of 1, 2 or 3 heating / cooling periods. For each heating / cooling pe-
riod, the start time, end time and comfort setpoint are to be entered.
In between heating / cooling periods, it is always the same economy temperature set-
point that is used. This economy temperature setpoint can be adjusted on the tempera-
ture menu.
2261
Z
0
2
16
°C
18
20
22
08
10
18
22
h
Heizphase 1
Heizphase 2
The holiday function is to be selected on the user menu. Set the start of the holiday
period (day of departure /
/
weekday), the duration of the holiday period and
the temperature setpoint (
). This will enable the controller to maintain the adjusted
temperature for a period of up to 99 days. Every day at midnight, the counter subtracts
one day.
When the holiday period is over, the counter reads 00, and the controller will automati-
cally resume the operating mode selected last.
To be flexible, the REV23RF has no connection facility for remote operation.
Switching
times
Temperatures in ° C
1st
period
2nd
period
3rd
period
Oper-
ating
mode
Block /
week-
days
1st period
2nd period
3rd period
Auto
1-5
Mo-Fr
6-7
Sa-Su
06:00
07:00
08:00
23:00
11:00
13:00
17:00
22:00
19
19
23
23
20
23
21
23
16
16
29
29
1-7
Mo-Su
00:00 24:00
19 23
1-7
Mo-Su
00:00 24:00
16 29
1-7
Mo-Su
00:00 24:00
5 35
Absence
12 30
Switching program
Example with 2 heating
periods per day
Holiday function
Remote operation
Factory settings