RDX42.22U Room Temperature Controller with LCD
Technical Instructions
Document Number 155-747
March 13, 2008
Siemens Industry, Inc.
Page 7
Table 3. Control Parameters.
Parameter
Meaning
Setting Range
Factory
Setting
P01
Heating setpoint in Energy Saving
mode (operating mode changeover
switch activated)
OFF, 46°F to 64.5°F (8°C to 18
°
C) (in
increments of 1°F)
61°F (16°C)
P02
Cooling setpoint in Energy Saving
mode (operating mode changeover
switch activated)
OFF, 75°F to 95°F (24°C to 35
°
C) (in
increments of 1°F)
82.5°F
(28°C)
P03
Minimum setpoint in Normal mode
46°F to 68°F (8°C to 20°C) (in
increments of 2°F)
46°F (8°C)
P04
Maximum setpoint in Normal mode
70°F to 95°F (21°C to 35°C) (in
increments of 2°F)
95°F (35°C)
P05
Minimum compressor off-time
1 to 10 minutes (in increments of
1 min)
3 min
P06
Minimum compressor on-time
1 to 10 minutes (in increments of
1 min)
1 min
P07
Auxiliary heater minimum hold time
1 to 10 minutes (in increments of
1 min)
1 min
P08
Fan overrun after auxiliary heater off
30 to 300 seconds (in increments of
10 seconds)
30 s.
P09
Sensor calibration
–3 to 3 K (in increments of 0.5 K)
(0.5 K = °F)
0 K
P10
Switching differential in heating mode
0.5 to 4 K (in increments of 0.5 K)
(0.5 K = °F)
2 K
P11
Switching differential in cooling mode
0.5 to 4 K (in increments of 0.5 K)
(0.5 K = °F)
1 K
P12
Setpoint differential between heating
and auxiliary heating W
D
0.5 to 5 K (in increments of 0.5 K)
(0.5 K = °F)
2 K
P13
Value of current room temperature
No setting, display only
—
P14
Active temperature sensor (display
only, no setting choices)
1: Room temperature sensor active
2: Return temperature sensor active
—